Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Inovance AM600. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Website: http://www.inovance.cn/
HMI Setting
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | Inovance AM600 | ||
| PLC I/F | RS485 4W | ||
| Baud rate | 9600 | 9600 ~ 115200 | |
| Data bits | 8 | ||
| Parity | Even | ||
| Stop bits | 1 | ||
| PLC sta. no. | 1 |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | Q | DDDDo | 0 ~ 81917 | |
| B | I | DDDDo | 0 ~ 81917 | |
| B | SM | DDDD | 0 ~ 7999 | |
| W | MW | DDDDD | 0 ~ 65535 | |
| W | SD | DDD | 0 ~ 7999 |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
Diagram 1: RS-485 2W (CN1 COM0 RS485 2W)
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS485 2W 9P D-Sub Female |
|
| Data- | ↔ (bidirectional) | 1 Data- |
| Data+ | ↔ (bidirectional) | 2 Data+ |
| GND | ↔ (bidirectional) | 5 GND |
Diagram 2: RS-485 2W (CN1 COM1 RS485 2W)
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS485 2W 9P D-Sub Female |
|
| Data- | ↔ (bidirectional) | 6 Data- |
| Data+ | ↔ (bidirectional) | 9 Data+ |
| GND | ↔ (bidirectional) | 3 GND |