The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with HUST H4C. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: HUST CNC Controller H4C, H6C Series

Website: http://www.hust.com.tw/

HMI Settings

Parameters Recommended Options Notes
PLC type HUST H4C
PLC I/F RS-232 CPU port
Baud rate 38400 9600, 19200, 38400, 57600
Data bits 7
Parity Even
Stop bits 2
Turn around delay 5
PLC sta. no. 1

Device Address

Bit/Word Device type Format Range Memo
B I DDD 0 ~ 255 Mapping to VM 10800 ~ 10807 (read only)
B O DDD 0 ~ 255 Mapping to VM 10808 ~ 10815 (read only)
B C DDD 0 ~ 255 Mapping to VM 10816 ~ 10823 (read only)
B S DDD 0 ~ 255 Mapping to VM 10824 ~ 10831 (read only)
B A DDD 0 ~ 1023 Mapping to VM 10832 ~ 10863 (read only)
B VM_bit DDDDDdd 0 ~ 9999931 Bit address (dd): 00 ~ 31
DW VM DDDDD 0 ~ 99999 Please refer to the controller specification for register range.
DW R DDD 0 ~ 255 Mapping to VM 10000 ~ 10255 (read only)
DW Cn DDD 0 ~ 255 Mapping to VM 10256 ~ 10511 (read only)
DW Tm DDD 0 ~ 255 Mapping to VM 10512 ~ 10767 (read only)

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232

HMI Direction PLC
Pin assignments RS232
9P D-Sub Male
Rx ↔ (bidirectional) 2
Tx ↔ (bidirectional) 3
GND ↔ (bidirectional) 5
↕︎ (tie) 7
8