The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Fuji NB Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

HMI Settings

Parameters Recommended Options Notes
PLC typeFuji NB Series
PLC I/FRS485 4W
Baud rate19200
Data bits8
ParityOdd
Stop bits1
PLC sta. no.0

PLC Settings

Parameter Value
Communication modeNITP Protocol / PLC Password (default is 0)

Device Addresses

Bit/Word Device Type Format Range Memo
BYHHH0 ~ 7ffOutput Relay
BXHHH0 ~ 3ffInput Relay
BMHHH0 ~ fffInternal Relay
BLHHH0 ~ fffLatch Relay
BCHH0 ~ ffCounter
BM_SpeHHHH0 ~ 81ffSpecial Relay
BTHHH0 ~ 1ffTimer
WTVHHH0 ~ 3ffTimer value
WCVHHH0 ~ 3ffCounter value
WDHHHH0 ~ 1fffData Register
WD_SpeHHHH0 ~ 81ffSpecial Register

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-485 4W (Fuji NB Series RS422 8P RJ45 Male)

HMI Direction PLC
Pin assignmentsFuji NB Series
RS422 8P RJ45
Male
Rx-↔ (bidirectional)4
RX+↔ (bidirectional)3
Tx-↔ (bidirectional)6
Tx+↔ (bidirectional)5
GND↔ (bidirectional)