Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with CANbus 2.0A/2.0B General and SAE J1939. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported series: CAN Bus 2.0A / CAN Bus 2.0B / SAE J1939
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | CAN Bus 2.0A/2.0B General and SAE J1939 | General / SAE J1939 | |
| Baud rate | 250K | 20K~1M | |
| Reset RDO when communication fails | |||
| Online simulator | NO | ||
| Extend address mode | NO |

How to Import SAE J1939 Address Tags
-
Add CANBus driver
In EBPro (EasyBuilder Pro) add the CAN Bus 2.0A/2.0B General and SAE J1939 driver. -
Open Address Tag Library
Open Address Tag Library, select User-defined tags and then click New.
-
Configure tag name and PLC
Set the following fields:nn- Name: Enter the tag name.n- PLC: Select the SAE J1939 device.n- Address type: Select Bit or Word.nnFor Transmission rate: if Use the default is selected, the HMI will wait for the reply from the CAN device. If Request mode is selected, the HMI will send a polling packet.nnAfter entering the above information, click Settings.
-
Set CAN device parameters
Set the following parameters according to the specification of the CAN device used.
-
Exit and review tags
After building the tags, click Exit.
Device Address
| Bit/Word | Device type | Format | Memo |
|---|---|---|---|
| B | DATA_Bit | HHHHHHHHBb | H: ID B: Byte position (1~8) b: Bit start position (1~8) |
| W | DATA | HHHHHHHHBbNN | H: ID B: Byte position (1~8) b: Bit start position (1~8) NN: Bit no. (1~64) |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | CAN Bus Device | |
| CAN- | ↔ (bidirectional) | CAN- |
| CAN+ | ↔ (bidirectional) | CAN+ |
| GND | ↔ (bidirectional) | GND |
To minimize signal reflection on the CAN bus network, termination resistors should be installed at both ends of the network, as shown in the following figure.

