Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Beckhoff ADS (Absolute Addressing). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: Twincat
HMI Setting
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | Beckhoff ADS (Absolute Addressing) | ||
| PLC I/F | RS232 | ||
| Baud rate | 38400 | ||
| Data bits | 8 | ||
| Parity | Even | ||
| Stop bits | 1 | ||
| ADS Port | 800 | 300, 800, 801, 811, 821, 831, 851 ~ 854 |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | IX |
DDDDDo |
0 ~ 655357 | |
| B | QX |
DDDDDo |
0 ~ 655357 | |
| B | MX |
DDDDDo |
0 ~ 655357 | |
| Byte | IB |
DDDDD |
0 ~ 65535 | |
| Byte | QB |
DDDDD |
0 ~ 65535 | |
| Byte | MB |
DDDDD |
0 ~ 65535 | |
| W | IW |
DDDDD |
0 ~ 65535 | |
| W | QW |
DDDDD |
0 ~ 65535 | |
| W | MW |
DDDDD |
0 ~ 65535 | |
| DW | ID |
DDDDD |
0 ~ 65535 | |
| DW | QD |
DDDDD |
0 ~ 65535 | |
| DW | MD |
DDDDD |
0 ~ 65535 | |
| DW | ID_FLOAT |
DDDDD |
0 ~ 65535 | |
| DW | QD_FLOAT |
DDDDD |
0 ~ 65535 | |
| DW | MD_FLOAT |
DDDDD |
0 ~ 65535 |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
RS-232
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS232 9P D-Sub Female |
|
| Rx | ↔ (bidirectional) | 3 TX |
| Tx | ↔ (bidirectional) | 2 RX |
| GND | ↔ (bidirectional) | 5 GND |