Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Yokogawa FA-M3 (Binary Mode, Ethernet). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: FA-M3 CPU SP35-5N, SP55-5N with F3LE01-5T/F3LE11-0T Ethernet

Protocol: Binary Mode (Ethernet)

Website: http://www.yokogawa.com/itc/itc-index-en.htm

HMI Setting

ParametersRecommendedOptionsNotes
PLC typeYOKOGAWA FA-M3 – Binary Mode (Ethernet)
PLC I/FEthernetTCP/UDP
Port no.12289
PLC sta. no.11 ~ 4

Device Address

Bit/WordDevice typeFormatRangeMemo
BXDDDDD1 ~ 71664
BYDDDDD1 ~ 71664
BIDDDDD1 ~ 65535
BEDDDD1 ~ 4096
BMDDDD1 ~ 9984
BLDDDDDD1 ~ 78192
BTUDDDD1 ~ 3072
BCUDDDD1 ~ 3072
WTPDDDD1 ~ 3072
WTIDDDD1 ~ 3072
WTSDDDD1 ~ 3072
WCPDDDD1 ~ 3072
WCIDDDD1 ~ 3072
WCSDDDD1 ~ 3072
WDDDDDD1 ~ 65535
WBDDDDDD1 ~ 262144
WFDDDDDD1 ~ 524288
WRDDDD1 ~ 4096
WZDDDD1 ~ 1024
WWDDDDD1 ~ 78192
WVDDD1 ~ 256

Wiring Diagram

The diagram below shows the Ethernet cable wiring.

Ethernet straight-through cable wiring showing all 8 conductors paired by color: W/Orange, Orange, W/Green, Blue, W/Blue, Green, W/Brown, and Brown, connected pin-to-pin on both ends.