Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Vigor VS Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: VIGOR VS Series and VS-ENET-EC Ethernet Module

Website: http://www.vigorplc.com.tw/

HMI Setting

Parameters Recommended Options Notes
PLC type VIGOR VS Series
PLC I/F RS485 2W RS232, RS485 2W, USB, Ethernet
Baud rate 19200 300 ~ 115200
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 0 0 ~ 254
Port no. 1000

*Support communications between HMI and PLC in pass-through mode

*Set LW-9903 to 2 to enhance the speed of download/upload PLC program in pass-through mode

PLC Setting

Protocol: VS Computer Link Slave (TCP or UDP Server)

Device Address

Bit/Word Device Type Format Range Memo
BXOOO0 ~ 571
BYOOO0 ~ 571
BMDDDD0 ~ 8191
BSDDDD0 ~ 4095
BSMDDDD9000 ~ 9511
BD_BitDDDDh0 ~ 8999f
BR_BitDDDDDh0 ~ 25999f
BT_CoilDDD0 ~ 511
BT_ContactDDD0 ~ 511
BC_CoilDDD0 ~ 255
BC_ContactDDD0 ~ 255
WXWOO0 ~ 21
WYWOO0 ~ 21
WMWDDD0 ~ 511
WSWDDD0 ~ 255
WDDDDD0 ~ 8999
WSDDDDD9000 ~ 9511
WRDDDDD0 ~ 25999
WTDDD0 ~ 511
WCDDD0 ~ 199
DWC_32BitDDD200 ~ 255

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232

HMI Direction PLC
Pin assignments CP2 RS232
terminal
Rx↔ (bidirectional)TX
Tx↔ (bidirectional)RX
GND↔ (bidirectional)SG

Diagram 2: RS-485 2W

HMI Direction PLC
Pin assignments CP1 RS485 2W
terminal
Data-↔ (bidirectional)D-
Data+↔ (bidirectional)D+
GND↔ (bidirectional)SG