Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Vigor M Series, VB Series, VH Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: VIGOR M Series, VB Series, VH Series
Website: http://www.vigorplc.com.tw/
HMI Setting
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | VIGOR | ||
| PLC I/F | RS485 2W | RS232, RS485 4W | |
| Baud rate | 19200 | ||
| Data bits | 8 | Select “7” for V1.10 and previous versions. | |
| Parity | None | Select “Even” for V1.10 and previous versions. | |
| Stop bits | 1 | ||
| PLC sta. no. | 0 | ||
| Extend address mode | NO |
NOTE: Support communications between HMI and PLC in pass-through mode.
NOTE: Set LW-9903 to 2 to enhance the speed of download/upload PLC program in pass-through mode.
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | X | OOO | 0 ~ 377 | |
| B | Y | OOO | 0 ~ 377 | |
| B | M | DDDD | 0 ~ 7999 | |
| B | T | DDD | 0 ~ 255 | |
| B | C | DDD | 0 ~ 255 | |
| B | SM | DDDD | 9000 ~ 9255 | |
| B | S | DDD | 0 ~ 999 | |
| W | TV | DDD | 0 ~ 255 | |
| W | CV | DDD | 0 ~ 199 | |
| W | D | DDDD | 0 ~ 9255 | |
| W | CV2 | DDD | 200 ~ 255 | |
| W | SD | DDDD | 9000 ~ 9255 |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
Diagram 1: RS-232
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS232 9P D-Sub Male |
|
| Rx | ↔ (bidirectional) | 3 TX |
| Tx | ↔ (bidirectional) | 2 RX |
| GND | ↔ (bidirectional) | 5 GND |
Diagram 2: RS-485 4W
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS485 4W 6P Mini-DIN Male |
|
| Rx- | ↔ (bidirectional) | TX- |
| RX+ | ↔ (bidirectional) | TX+ |
| Tx- | ↔ (bidirectional) | RX- |
| Tx+ | ↔ (bidirectional) | RX+ |
| GND | ↔ (bidirectional) | SG |