The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Vigor M Series, VB Series, VH Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: VIGOR M Series, VB Series, VH Series

Website: http://www.vigorplc.com.tw/

HMI Setting

Parameters Recommended Options Notes
PLC type VIGOR
PLC I/F RS485 2W RS232, RS485 4W
Baud rate 19200
Data bits 8 Select “7” for V1.10 and previous versions.
Parity None Select “Even” for V1.10 and previous versions.
Stop bits 1
PLC sta. no. 0
Extend address mode NO

NOTE: Support communications between HMI and PLC in pass-through mode.

NOTE: Set LW-9903 to 2 to enhance the speed of download/upload PLC program in pass-through mode.

Device Address

Bit/Word Device type Format Range Memo
BXOOO0 ~ 377
BYOOO0 ~ 377
BMDDDD0 ~ 7999
BTDDD0 ~ 255
BCDDD0 ~ 255
BSMDDDD9000 ~ 9255
BSDDD0 ~ 999
WTVDDD0 ~ 255
WCVDDD0 ~ 199
WDDDDD0 ~ 9255
WCV2DDD200 ~ 255
WSDDDDD9000 ~ 9255

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232

HMIDirectionPLC
Pin assignments RS232
9P D-Sub
Male
Rx↔ (bidirectional)3 TX
Tx↔ (bidirectional)2 RX
GND↔ (bidirectional)5 GND

Diagram 2: RS-485 4W

HMIDirectionPLC
Pin assignments RS485 4W
6P Mini-DIN
Male
Rx-↔ (bidirectional)TX-
RX+↔ (bidirectional)TX+
Tx-↔ (bidirectional)RX-
Tx+↔ (bidirectional)RX+
GND↔ (bidirectional)SG