Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with VEICHI VC Series PLC. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: VEICHI VC1S, VC1, VC2, VC3, VC5 PLC
Website: https://www.veichi.org/
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | VEICHI VC Series PLC | ||
| PLC I/F | RS485 2W | RS232/RS485 2W/Ethernet | |
| Baud rate | 9600 | 1200~115200 | |
| Data bits | 8 | ||
| Parity | Even | ||
| Stop bits | 1 | ||
| PLC sta. no. | 1 | ||
| Online simulator | YES |
Device Addresses
| Bit/Word | Device Type | Format | Range | Memo |
|---|---|---|---|---|
| B | X | OOO | 0 ~ 777 | |
| B | Y | OOO | 0 ~ 777 | |
| B | M | DDDD | 0 ~ 2047 | |
| B | M_EXT | DDDDD | 2048 ~ 10239 | |
| B | SM | DDD | 0 ~ 255 | |
| B | SM_EXT | DDDD | 256 ~ 1023 | |
| B | S | DDDD | 0 ~ 1023 | |
| B | S_EXT | DDDD | 1024 ~ 4095 | |
| B | TS | DDD | 0 ~ 255 | |
| B | TS_EXT | DDD | 256 ~ 511 | |
| B | CS | DDD | 0 ~ 255 | |
| B | CS_EXT | DDD | 256 ~ 511 | |
| W | D | DDDD | 0 ~ 7999 | |
| W | SD | DDD | 0 ~ 255 | |
| W | SD_EXT | DDDD | 256 ~ 1023 | |
| W | Z | DD | 0 ~ 15 | |
| W | TC | DDD | 0 ~ 255 | |
| W | TC_EXT | DDD | 256 ~ 511 | |
| W | CC | DDD | 0 ~ 199 | |
| DW | CC_32Bit | DDD | 200 ~ 263 | |
| W | R | DDDDD | 0 ~ 32767 | |
| DW | D_32Bit | DDDD | 0 ~ 7999 | |
| DW | SD_32Bit | DDD | 0 ~ 255 | |
| DW | SD_32Bit_EXT | DDDD | 256 ~ 1023 |
Wiring Diagrams
NOTE: The serial port pin assignments may vary between HMI models.
Diagram 1: RS-232
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS232 | |
| Rx | ↔ (bidirectional) | TXD |
| Tx | ↔ (bidirectional) | RXD |
| GND | ↔ (bidirectional) | GND |
Diagram 2: RS-485 2W
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS485 2W | |
| Data- | ↔ (bidirectional) | D- |
| Data+ | ↔ (bidirectional) | D+ |
| GND | ↔ (bidirectional) | GND |
Diagram 3: Ethernet