The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with VEICHI VC Series PLC. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: VEICHI VC1S, VC1, VC2, VC3, VC5 PLC

Website: https://www.veichi.org/

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeVEICHI VC Series PLC
PLC I/FRS485 2WRS232/RS485 2W/Ethernet
Baud rate96001200~115200
Data bits8
ParityEven
Stop bits1
PLC sta. no.1
Online simulatorYES

Device Addresses

Bit/WordDevice TypeFormatRangeMemo
BXOOO0 ~ 777
BYOOO0 ~ 777
BMDDDD0 ~ 2047
BM_EXTDDDDD2048 ~ 10239
BSMDDD0 ~ 255
BSM_EXTDDDD256 ~ 1023
BSDDDD0 ~ 1023
BS_EXTDDDD1024 ~ 4095
BTSDDD0 ~ 255
BTS_EXTDDD256 ~ 511
BCSDDD0 ~ 255
BCS_EXTDDD256 ~ 511
WDDDDD0 ~ 7999
WSDDDD0 ~ 255
WSD_EXTDDDD256 ~ 1023
WZDD0 ~ 15
WTCDDD0 ~ 255
WTC_EXTDDD256 ~ 511
WCCDDD0 ~ 199
DWCC_32BitDDD200 ~ 263
WRDDDDD0 ~ 32767
DWD_32BitDDDD0 ~ 7999
DWSD_32BitDDD0 ~ 255
DWSD_32Bit_EXTDDDD256 ~ 1023

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232

HMIDirectionPLC
Pin assignmentsRS232
Rx↔ (bidirectional)TXD
Tx↔ (bidirectional)RXD
GND↔ (bidirectional)GND

Diagram 2: RS-485 2W

HMIDirectionPLC
Pin assignmentsRS485 2W
Data-↔ (bidirectional)D-
Data+↔ (bidirectional)D+
GND↔ (bidirectional)GND

Diagram 3: Ethernet

Standard Ethernet cable wiring showing all 8 wire pairs color-coded: W/Orange, Orange, W/Green, Blue, W/Blue, Green, W/Brown, Brown on both ends.