Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Trio MODBUS RTU, TCP/IP. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeTrio MODBUS RTU, TCP/IP
PLC I/FRS485RS232/RS485/Ethernet
Baud rate96009600~115200
Data bits87, 8
ParityEvenEven, Odd, None
Stop bits11, 2
Port no.502
PLC sta. no.10-255
Online simulatorYES
Broadcast commandYES
Extend address modeYES

PLC Settings

ParameterValue
Communication modeModbus RTU protocol
PLC mode4 (16bit signed integer)

Device Address

Bit/WordDevice typeFormatRangeMemo
BVR_BitDDDDdd0 ~ 409615
BTable_BitDDDDDdd0 ~ 3199915
WVRDDDD0 ~ 4096
WTableDDDDD0 ~ 31999

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232

HMIDirectionPLC
Pin assignmentsRS232
9P D-Sub
Male
Rx↔ (bidirectional)TXD
Tx↔ (bidirectional)RXD
GND↔ (bidirectional)GND
↕︎ (tie)RTS
CTS

Diagram 2: RS-485 2W

HMIDirectionPLC
Pin assignmentsRS485 2W
9P D-Sub Male
Data-↔ (bidirectional)D-
Data+↔ (bidirectional)D+
GND↔ (bidirectional)GND

Diagram 3: RS-485 4W

HMIDirectionPLC
Pin assignmentsRS485 4W
9P D-Sub Male
Rx-↔ (bidirectional)TX-
RX+↔ (bidirectional)TX+
Tx-↔ (bidirectional)RX-
Tx+↔ (bidirectional)RX+
GND↔ (bidirectional)GND

Diagram 4: Ethernet

Use a standard straight-through Ethernet cable for TCP/IP connections.

Straight-through Ethernet cable wiring showing all 8 wire pairs matched pin-for-pin: W/Orange, Orange, W/Green, Blue, W/Blue, Green, W/Brown, Brown.