Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Toptek Topvert. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: TOPVERT G1/H1/P1 series
Website: http://www.toptek.biz/
HMI Setting
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | Toptek Topvert | ||
| PLC I/F | RS485 2W | ||
| Baud rate | 9600 | ||
| Data bits | 7 | ||
| Parity | None | ||
| Stop bits | 2 | ||
| PLC sta. no. | 1 | ||
| Online simulator | YES | ||
| Broadcast command | YES | ||
| Extend address mode | YES | ||
| Broadcast station no. | 0 |
PLC Setting
| Parameter | Value |
|---|---|
| Communication mode | Pr 7-15 = 0 (7, N, 2 ASCII) |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | PR_Bit | DDDDDdd | 0 ~ 6553515 | G=Groups, F=Function no. dd=0~15 bit no. |
| W | PR | DDDDD | 0 ~ 65535 | G=Groups, F=Function no. |
Notes
Max. read-command size (words): 16
Max. write-command size (words): 1
For G1/H1/P1 Series Inverter, if standard parameter address is in decimal = 100*G+F:
G=Group (parameter group code 0~9); F=Function no. (parameter number 0~99)
For example: Pr5-20 (decimal) parameter address is expressed as 100*5+20=520.
Parameter Address Examples
| Parameter (PrX-XX) | Address (decimal) |
|---|---|
0-00 | 0*100+0=0 |
0-14 | 0*100+14=14 |
1-00 | 1*100+0=100 |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
RS-485 2W
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS485 2W Terminal | |
| Data- | ↔ (bidirectional) | SG- |
| Data+ | ↔ (bidirectional) | SG+ |
| GND | ↔ (bidirectional) | GND |