Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with TECO Inverter. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: TECO Inverter series, 7300CV model
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | TECO Inverter | ||
| PLC I/F | RS232 | RS232/RS485 | |
| Baud rate | 38400 | ||
| Data bits | 8 | ||
| Parity | None | ||
| Stop bits | 1 | ||
| PLC sta. no. | 1 |
Device Address
| Bit/Word | Device | Format | Range | Memo |
|---|---|---|---|---|
| B | 0x | DDDDD | 1 ~ 65535 | Output Bit |
| B | 1x | DDDDD | 1 ~ 65535 | Input Bit (read only) |
| B | 3x_Bit | DDDDDdd | 100 ~ 6553515 | Input Register Bit (read only) |
| B | 4x_Bit | DDDDDdd | 100 ~ 6553515 | Output Register Bit |
| B | 6x_Bit | DDDDDdd | 100 ~ 6553515 | |
| B | 0x (0x0f) | DDDDD | 1 ~ 65535 | Write Multiple Coils |
| W | 3x | DDDDD | 1 ~ 65535 | Input Register (read only) |
| W | 4x | DDDDD | 1 ~ 65535 | Output Register |
| DW | 5x | DDDDD | 1 ~ 65535 | 4x Double Word Swap |
| W | 6x | DDDDD | 1 ~ 65535 | 4x Single Word Write |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
RS-232

| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS232 6P Mini-Din Male | |
| Rx | ↔ (bidirectional) | 3 TX |
| Tx | ↔ (bidirectional) | 4 RX |
| GND | ↔ (bidirectional) | 5 GND |