Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with TECO Inverter. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: TECO Inverter series, 7300CV model

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeTECO Inverter
PLC I/FRS232RS232/RS485
Baud rate38400
Data bits8
ParityNone
Stop bits1
PLC sta. no.1

Device Address

Bit/WordDeviceFormatRangeMemo
B0xDDDDD1 ~ 65535Output Bit
B1xDDDDD1 ~ 65535Input Bit (read only)
B3x_BitDDDDDdd100 ~ 6553515Input Register Bit (read only)
B4x_BitDDDDDdd100 ~ 6553515Output Register Bit
B6x_BitDDDDDdd100 ~ 6553515
B0x (0x0f)DDDDD1 ~ 65535Write Multiple Coils
W3xDDDDD1 ~ 65535Input Register (read only)
W4xDDDDD1 ~ 65535Output Register
DW5xDDDDD1 ~ 655354x Double Word Swap
W6xDDDDD1 ~ 655354x Single Word Write

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232

JNSIF-232 wiring diagram showing RS-232 connection from HMI through JNSIF-232 adapter to TECO 7300CV inverter CON2 12P port and three-phase power supply.
HMIDirectionPLC
Pin assignmentsRS232
6P Mini-Din Male
Rx↔ (bidirectional)3 TX
Tx↔ (bidirectional)4 RX
GND↔ (bidirectional)5 GND