Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Siemens S7-200 SMART Ethernet. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: Siemens S7/200 SMART Series Ethernet Module
Website: http://www.siemens.com/entry/cc/en/
HMI Setting
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | Siemens S7-200 SMART (Ethernet) | ||
| PLC I/F | Ethernet | ||
| Port no. | 102 | ||
| PLC sta. no. | 2 | ||
| Online simulator | Yes | ||
| Multiple HMI connection | Yes (8 HMI) |
NOTE: At most four HMIs can be connected with the PLC simultaneously.
Device Address
| Bit/Word | Device | Format | Range | Memo |
|---|---|---|---|---|
| B | I |
DDDDo | 0 ~ 12797 | Input |
| B | Q |
DDDDo | 0 ~ 12797 | Output |
| B | M |
DDo | 0 ~ 637 | Bit Memory |
| B | V |
DDDDDDo | 0 ~ 1023997 | V Memory Bit |
| B | S |
DDo | 0 ~ 317 | SCR |
| B | SM |
DDDDo | 0 ~ 20477 | Special Memory Bit |
| B | Timer |
DDD | 0 ~ 511 | Timer |
| B | Counter |
DDD | 0 ~ 511 | Counter |
| W | IW |
DDDD | 0 ~ 1278 | Input |
| W | QW |
DDDD | 0 ~ 1278 | Output |
| W | MW |
DD | 0 ~ 62 | Word Memory |
| W | VW |
DDDDDD | 0 ~ 102398 | V Memory |
| W | SW |
DD | 0 ~ 30 | SCR |
| W | SMW |
DDDD | 0 ~ 2046 | Special Memory |
| W | T |
DDD | 0 ~ 511 | Timer |
| W | C |
DDD | 0 ~ 511 | Counter |
| W | AIW |
DDD | 0 ~ 530 | Analog Input |
| W | AQW |
DDD | 0 ~ 530 | Analog Output |
| Byte | IB |
DDDD | 0 ~ 1279 | Input (Byte) |
| Byte | QB |
DDDD | 0 ~ 1279 | Output (Byte) |
| Byte | MB |
DD | 0 ~ 63 | Memory (Byte) |
| Byte | VB |
DDDDDD | 0 ~ 102399 | V Memory (Byte) |
| Byte | SB |
DD | 0 ~ 31 | SCR (Byte) |
| Byte | SMB |
DDDD | 0 ~ 2047 | Special Memory (Byte) |
| DW | ID |
DDDD | 0 ~ 1276 | Input (Double Word) |
| DW | QD |
DDDD | 0 ~ 1276 | Output (Double Word) |
| DW | MD |
DD | 0 ~ 60 | Memory (Double Word) |
| DW | VD |
DDDDDD | 0 ~ 102396 | V Memory (Double Word) |
| DW | SD |
DD | 0 ~ 28 | SCR (Double Word) |
| DW | SMD |
DDDD | 0 ~ 2044 | Special Memory (Double Word) |
NOTE: Double word and floating point value must use VD device type.
Wiring Diagram
The diagram below shows the Ethernet cable wiring.