Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Phoenix Contact ProConOS (Absolute Addressing). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: KW ProConOS

Website: https://www.phoenixcontact.com/online/portal/pc

HMI Settings

ParametersRecommendedNotes
PLC typeKW ProConOS (Absolute Addressing)
PLC I/FEthernet
Port no.20547

Device Address

Bit/WordDevice typeFormatRangeMemo
BIXDDDDDo0 ~ 655357Input %IX
BQXDDDDDo0 ~ 655357Output %QX
BMXDDDDDDDDo0 ~ 518326727%MX
WIW_EVENDDDDD0 ~ 65535%IW (must be even)
WQW_EVENDDDDD0 ~ 65535%QW (must be even)
WMW_EVENDDDDDDDD0 ~ 51832672%MW (must be even)
DWID_EVENDDDDD0 ~ 65535%ID (must be even)
DWQD_EVENDDDDD0 ~ 65535%QD (must be even)
DWMD_EVENDDDDDDDD0 ~ 51832672%MD (must be even)
ByteIBDDDDD0 ~ 65535
ByteQBDDDDD0 ~ 65535
ByteMBDDDDDDDD0 ~ 51832672
WIWDDDDD0 ~ 65535%IW
WQWDDDDD0 ~ 65535%QW
WMWDDDDDDDD0 ~ 51832672%MW
DWIDDDDDD0 ~ 65535%ID
DWQDDDDDD0 ~ 65535%QD
DWMDDDDDDDDD0 ~ 51832672%MD
WSTRINGDDDDDDDD0 ~ 51832672

Wiring Diagram

The diagram below shows the Ethernet cable wiring.

Ethernet straight-through cable wiring diagram showing all 8 color-coded wire pairs connected pin-to-pin from one end to the other.