The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Motrona CT-150. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: motrona CT-150

Website: http://motrona.net/index.html

HMI Setting

Parameters Recommended Options Notes
PLC type motrona CT-150
PLC I/F RS232 RS232/RS485
Baud rate 9600 1200 ~ 38400
Data bits 7 7, 8
Parity Even Even, Odd, None
Stop bits 1 1, 2
PLC sta. no. 11 11 ~ 99 The station number must not contain 0.

Device Address

Bit/Word Device type Format Range
W An D 4 ~ 8
W Bn D 1 ~ 9
W Cn DD 0 ~ 99
W An_32Bit D 4 ~ 8
W Bn_32Bit D 1 ~ 9
W Cn_32Bit DD 0 ~ 99
W ERR_CNT D 0
W LV_VAL D 0
W PRTMARK_ERR D 0
W BAT_CNT D 0
W WASTE_CNT D 0
W LINE_SPD D 0
W ACT_CUT_LEN D 0
W ACT_CUT_ERR_M D 0
W ACT_CUT_ERR_L D 0

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232

HMI Direction PLC
Pin assignments RS232
9P D-Sub
Female
Rx ↔ (bidirectional) 3 TXD
Tx ↔ (bidirectional) 2 RXD
GND ↔ (bidirectional) 5 GND