All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Mitsubishi L6ADP CPU. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Mitsubishi L6ADP CPU RS232 Series Port

Website: http://www.mitsubishi-automation.com

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeMitsubishi L6ADP
PLC I/FRS232
Baud rate115200
Data bits8
ParityOdd
Stop bits1
PLC sta. no.1
Online simulatorYES
Extend address modeNO
Pass-ThroughYES

NOTE: Communications between HMI and PLC in pass-through mode are not supported.

NOTE: Set LW-9903 to 2 to enhance the speed of download/upload PLC program in pass-through mode.

Device Address

Bit/WordDeviceFormatRangeMemo
BSMDDDD0 ~ 2047Special Int. Relays
BXHHHH0 ~ 1FFFInput Relay
BYHHHH0 ~ 1FFFOutput Relay
BMDDDD0 ~ 8191Internal Relay
BLDDDD0 ~ 8191Latch Relay
BFDDDD0 ~ 2047Annunciator
BVDDDD0 ~ 2047Edge Relay
BBHHHH0 ~ 1FFFLink Relay
BSBHHH0 ~ 7FFSpecial Link Relay
BD_BitDDDDDDh0 ~ 143359FData Register bit
WSDDDDD0 ~ 2047Special register
WDDDDDDD0 ~ 143359Data Register
WWHHHH0 ~ 1FFFLink Register
WSWHHH0 ~ 7FFSpecial Link Register
WZDD0 ~ 19Index Register
WCDDDD0 ~ 2047Counter
WTDDDD0 ~ 1023Timer

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

The following is the view from the soldering point of a connector.

6-pin circular connector pinout for Mitsubishi L6ADP communication port, with pins numbered 1 through 6.

Diagram 1 — RS-232

HMIDirectionPLC
Pin assignmentsRS232
6P Mini-Din Male
Rx↔ (bidirectional)3
Tx↔ (bidirectional)4
GND↔ (bidirectional)5