Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Mitsubishi FX2N PLC. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Mitsubishi FX2N series PLC

Website: http://www.mitsubishi-automation.com

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeMitsubishi FX2N
PLC I/FRS485 4WRS232/RS485
Baud rate192009600/19200/38400/57600/115200
Data bits7
ParityEven
Stop bits1
PLC sta. no.0
Online simulatorYES
Extend address modeNO

NOTE: Supports communications between HMI and PLC in pass-through mode.

NOTE: Set LW-9903 to 2 to enhance the speed of download/upload PLC program in pass-through mode.

Device Address

Bit/WordDevice TypeFormatRangeMemo
BXOOO0 ~ 377Input Relay
BYOOO0 ~ 377Output Relay
BMDDDD0 ~ 7999Auxiliary Relay
BTDDD0 ~ 255Timer Relay
BCDDD0 ~ 255Counter Relay
BSMDDDD8000 ~ 9999Special Auxiliary Relay
BD_BitDDDDdd0 ~ 7999.15Data Register Bit (D)
BSDDDD0 ~ 4095State Relay (S)
WTVDDD0 ~ 255Timer Memory
WCVDDD0 ~ 199Counter Memory
WDDDDD0 ~ 7999Data Register
DWCV2DDD200 ~ 255Counter Memory (D Word)
WSDDDDD8000 ~ 9999Special Data Register

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

The following is the view from the soldering point of a connector.

8-pin Mini-Din male connector pinout diagram showing the soldering-point view of the RS422 serial port on the Mitsubishi FX2N PLC.

RS-485 4W (RS422 Port 8P Mini-Din Male)

HMIDirectionPLC
Pin assignmentsRS422
Port 8P Mini-Din
Male
Rx-↔ (bidirectional)4
RX+↔ (bidirectional)7
Tx-↔ (bidirectional)1
Tx+↔ (bidirectional)2
GND↔ (bidirectional)3