Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Mitsubishi A2US. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: Mitsubishi A2US
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | Mitsubishi A2US | ||
| PLC I/F | RS232 | ||
| Baud rate | 9600 | ||
| Data bits | 8 | ||
| Parity | Odd | ||
| Stop bits | 1 | ||
| PLC sta. no. | 0 |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | X | HHHH | 0 ~ 270f | Input Relay |
| B | Y | HHHH | 0 ~ 270f | Output Relay |
| B | M | DDDD | 0 ~ 9999 | Auxiliary Relay |
| W | TV | DDD | 0 ~ 255 | Timer Memory |
| W | CV | DDD | 0 ~ 255 | Counter Memory |
| W | D | DDDD | 0 ~ 9999 | Data Register |
Wiring Diagrams
NOTE: Due to hardware limitations, this PLC is not supported by HMI models without RTS/CTS.
Use the RS422 to RS232 PLC programming cable (shown as follows).

NOTE: The serial port pin assignments may vary between HMI models.
Diagram 1
RS-232
| HMI | PLC Programming Converter | PLC |
|---|---|---|
| Pin assignments | RS422 25P D-Sub Male | |
| Rx | TX / TX+ | 2 RX+ |
| Tx | RX / RX+ | 3 TX+ |
| GND | GND / DTR+ | 4 DSR+ |
| RTS | CTS / GND | 7 GND |
| CTS | RTS / TX- | 15 RX- |
| RX- | 16 TX- | |
| DTR- | 17 DSR- |
Diagram 2
cMT-G01, cMT-G02, cMT-SVR-100/200, cMT-FHDX-820, cMT-SVRX-820 connection diagram.
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | A Series PLC CPU 25 pin RS485-4W | |
| 8 TX+ | ↔ (bidirectional) | 2 RX+ |
| 9 TX- | ↔ (bidirectional) | 15 RX- |
| 6 RX+ | ↔ (bidirectional) | 3 TX+ |
| 7 RX- | ↔ (bidirectional) | 16 TX- |
| 1 Data+ | ↔ (bidirectional) | 4 CTS+ |
| 4 Data- | ↔ (bidirectional) | 17 CTS- |
| 5 GND | ↔ (bidirectional) | 7 GND |
| ↕︎ (tie) | 20 21 Short |