The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with MIKOM MX Series PLC. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Support series: MIKOM MX series PLC

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeMIKOM MX Series PLC
PLC I/FRS232RS232/485/Ethernet
Baud rate192009600~115200
Data bits88
ParityEvenNone, Even, Odd
Stop bits11, 2
PLC sta. no.10~31
Online simulatorYES

PLC Settings

PORT 0 (RS232) 115200

PORT 1 (RS485) 19200

Device Address

Bit/WordDevice TypeFormatRangeMemo
BYDDD0~777Output Relay
BXDDD0~777Input Relay
BMDDDD0~4095Auxiliary Relay
BSMDDD0~511Special Auxiliary Relay
BSDDDD0~1535Step Relay
BTDDD0~511Timer Relay
BCDDD0~511Counter Relay
BD_BitDDDDDdd0~3276715Data Register Bit
WDDDDDD0~32767Data Register
WSDDDD0~511Special Data Register
WZDDD0~255Indexed Addressing Register
WTVDDD0~511Timer
WCVDDD0~199Counter
DWC_32BitDDD200~511Counter
WU0DDD0~199Special Module Register
WU1DDD0~199Special Module Register
WU2DDD0~199Special Module Register
WU3DDD0~199Special Module Register
WU4DDD0~199Special Module Register
WU5DDD0~199Special Module Register
WU6DDD0~199Special Module Register
WU7DDD0~199Special Module Register

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

8-pin circular DIN connector pinout for MIKOM MX series PLC serial communication port, pins numbered 1 through 8.

The view from the soldering point of a connector.

RS-232

HMIDirectionPLC
Pin assignmentsRS232
8P Mini-DIN
Male
Rx↔ (bidirectional)3
Tx↔ (bidirectional)2
GND↔ (bidirectional)5

Ethernet

Standard Ethernet straight-through cable wiring diagram showing T568B color-coded pairs on both ends.