The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with LS Electric GLOFA FEnet (Ethernet). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeLS GLOFA FEnet (Ethernet)
PLC I/FEthernet
Port no.2004
PLC sta. no.00~31

Device Addresses

Bit/WordDevice TypeFormatRangeMemo
BMXDDDDDD0 ~ 131056Internal Relay
BIXddDdd0 ~ 63763Input
BQXddDdd0 ~ 63763Output
WMWDDDD0 ~ 8191Data Register
DWMDDDDD0 ~ 4095Double Word

Wiring Diagram

The diagram below shows the Ethernet cable wiring.

Straight-through Ethernet cable wiring diagram showing all 8 conductors color-coded: W/Orange, Orange, W/Green, Blue, W/Blue, Green, W/Brown, Brown paired pin-to-pin.