Connection Parameters Needed for HMI/cMT Products to Communicate with Leadshine mPLC2 Modbus RTU, TCP/IP using EBPro (EasyBuilder Pro)
Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Leadshine mPLC2 Modbus RTU, TCP/IP. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: LEADSHINE mPLC2
HMI Settings
Parameters
Recommended
Options
Notes
PLC type
LEADSHINE mPLC2 Modbus RTU,TCP/IP
PLC I/F
RS232
RS232/RS485 2W/Ethernet
Baud rate
9600
9600 ~ 115200
Data bits
8
7, 8
Parity
None
None, Odd, Even
Stop bits
1
1, 2
Port no.
502
PLC sta. no.
1
1 ~ 247
Device Addresses
Bit/Word
Device type
Format
Range
Memo
B
M
DDDD
0 ~ 8511
B
X
OOOO
0 ~ 1777
B
Y
OOOO
0 ~ 1777
B
S
DDDD
0 ~ 4095
B
T
DDD
0 ~ 511
B
C
DDD
0 ~ 255
B
F
DDDD
0 ~ 7999
B
B
DDDDD
0 ~ 16383
B
L
DDDDD
0 ~ 16383
B
D
DDDD
0 ~ 8511
B
R
DDDDD
0 ~ 16383
B
VD
DDDDD
0 ~ 16383
B
RD
DDDDD
0 ~ 16383
B
TW
DDD
0 ~ 511
B
CW
DDD
0 ~ 199
B
CD
DDD
200 ~ 255
Wiring Diagrams
NOTE: The serial port pin assignments may vary between HMI models.