Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with HollySys LE/LM PLC. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: HollySys LE/LM series PLC

Website: http://www.hollysys.com/

HMI Setting

ParametersRecommended OptionsNotes
PLC typeHollySys LE/LM PLC
PLC I/FRS485 2W
Baud rate38400
Data bits8
ParityNone
Stop bits1
PLC sta. no.1

Device Address

Bit/WordDevice typeFormatRangeMemo
B%IXDDDDo0 ~ 81907
B%MXDDDDo0 ~ 81907
B%QXDDDDo0 ~ 81907
W%IWDDDD0 ~ 8190
W%QWDDDD0 ~ 8190
W%MWDDDD0 ~ 8190
W%MDDDDD0 ~ 8190
W%MRDDDD0 ~ 8190

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-485 2W

The following is the view from the soldering point of a connector.

8-pin circular DIN connector pinout for HollySys LE/LM PLC serial communication port, pins numbered 1 through 8.
HMIDirectionPLC
Pin assignmentsRS485 2W
8P Mini-Din Male
Data-↔ (bidirectional)6
Data+↔ (bidirectional)5
GND↔ (bidirectional)7