Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with HollySys LE/LM PLC. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: HollySys LE/LM series PLC
Website: http://www.hollysys.com/
HMI Setting
| Parameters | Recommended Options | Notes |
|---|---|---|
| PLC type | HollySys LE/LM PLC | |
| PLC I/F | RS485 2W | |
| Baud rate | 38400 | |
| Data bits | 8 | |
| Parity | None | |
| Stop bits | 1 | |
| PLC sta. no. | 1 |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | %IX | DDDDo | 0 ~ 81907 | |
| B | %MX | DDDDo | 0 ~ 81907 | |
| B | %QX | DDDDo | 0 ~ 81907 | |
| W | %IW | DDDD | 0 ~ 8190 | |
| W | %QW | DDDD | 0 ~ 8190 | |
| W | %MW | DDDD | 0 ~ 8190 | |
| W | %MD | DDDD | 0 ~ 8190 | |
| W | %MR | DDDD | 0 ~ 8190 |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
RS-485 2W
The following is the view from the soldering point of a connector.

| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS485 2W 8P Mini-Din Male | |
| Data- | ↔ (bidirectional) | 6 |
| Data+ | ↔ (bidirectional) | 5 |
| GND | ↔ (bidirectional) | 7 |