Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Hengtong HT_EMS. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: HT_EMS

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeHT_EMS
PLC I/FRS232
Baud rate115200
Data bits8
ParityNone
Stop bits1
PLC sta. no.0
Online simulatorYES
Extend address modeYES

Device Address

Bit/WordDevice typeFormatRangeMemo
BEMS BitDDDDDdd0 ~ 3276715EMS bit
WEMSDDDD0 ~ 1023
WPCSDDDD0 ~ 1023
WSTSDDDD0 ~ 1023
WCentral control PositiveDDDD0 ~ 1023*Note1, *Note4
WCentral control NegativeDDDD0 ~ 1023*Note1, *Note4
WBattery stackDDDD0 ~ 1023
WBattery clusterDDDD0 ~ 1023
WPV INVDDDD0 ~ 1023
WPV junction boxDDDD0 ~ 1023
WDC charging pileDDDD0 ~ 1023
WAC charging pileDDDD0 ~ 1023
WGrid gateway meterDDDD0 ~ 1023
WESS gateway meterDDDD0 ~ 1023
WPV INV gateway meterDDDD0 ~ 1023
WCharging pile gatewayDDDD0 ~ 1023
WWind energy gatewayDDDD0 ~ 1023
WLoad gateway meterDDDD0 ~ 1023
WACDCDDDD0 ~ 1023
WDCDCDDDD0 ~ 1023
WAir-conditionDDDD0 ~ 1023
WFire fightingDDDD0 ~ 1023
WUPSDDDD0 ~ 1023
WDiesel engineDDDD0 ~ 1023
WEQP_LISTDDDD0 ~ 1023*Note2
WSYS_INFODDDD0 ~ 1023*Note2
WSYS_TIMED0 ~ 5*Note1, *Note3
WESS inside meterDDDD0 ~ 1023
WDynamic Station NumberD0 ~ 2*Note5
WHigh voltage side meterDDDD0 ~ 1023

Note1: Only Central control Positive, Central control Negative, SYS_TIME can be written.

Note2: EQP_LIST, SYS_INFO only support ASCII object.

Note3: SYS_TIME year (SYS_TIME-1) is necessary to be more than 2000. When its values are written, PLC will update every 500 ms, so it may display the previous value once or twice.

Note4: Central control Positive, Central control Negative write in same address. The only difference between two address types is the write type.

Note5: Address 0: enable=1, disable=0. Address 1: PV INV station. Address 2: Battery cluster station. After the dynamic station number function is enabled at address 0, you can use address 1 and address 2 to specify the PV INV and Battery cluster communication station numbers.

Note6: To query the third device, you need to set the object address to 2#. For example, DC Charge pile with the signal ID 1 of the third device, set it to 2#1.

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232

HMIDirectionPLC
Pin assignmentsRS232
9P D-sub
Rx↔ (bidirectional)2 TXD
Tx↔ (bidirectional)3 RXD
GND↔ (bidirectional)5 GND