The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Fatek FB/FBs/B1/B1z Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: FATEK FB/FBs/B1/B1z series, FB MC series, and FB MA series need

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeFATEK FB/FBs/B1/B1z Series
PLC I/FRS232RS232/RS485/Ethernet
Baud rate9600
Data bits7
ParityEven
Stop bits1
PLC sta. no.10–255Must match PLC port setting.
Port no.500Ethernet only.

NOTE: Supports communications between HMI and PLC in pass-through mode. Set LW-9903 to 2 to enhance the speed of download/upload PLC program in pass-through mode.

Device Address

Bit/WordDevice TypeFormatRangeMemo
BXDDDD0 ~ 9999Input
BYDDDD0 ~ 9999Output
BMDDDD0 ~ 9999Internal Relay
BSDDDD0 ~ 9999Step Relay
BTDDDD0 ~ 9999Timer
BCDDDD0 ~ 9999Counter
BPLC_MODED0PLC mode
BR_BitDDDDdd0 ~ 999915
BD_BitDDDDdd0 ~ 999915
BT_FBeDDDD0 ~ 9999Timer for FBe Model
BC_FBeDDDD0 ~ 9999Counter for FBe Model
WRTDDDD0 ~ 9999Timer Register
WRCDDDD0 ~ 9999Counter Register
WRDDDD0 ~ 9999Data Register
WDDDDD0 ~ 9999Data Register
WDRTDDDD0 ~ 9999Double Word Timer Register
WDRCDDD200 ~ 255Double Word Counter Register
WWXDDDD0 ~ 9999Input Word (8-bit)
WWYDDDD0 ~ 9999Output Word (8-bit)
WWMDDDD0 ~ 9999Internal Relay Word (8-bit)
WWSDDDD0 ~ 9999(8-bit)
WFRDDDD0 ~ 9999
WWX_16BITDDDD0 ~ 9999
WWY_16BITDDDD0 ~ 9999
WWM_16BITDDDD0 ~ 9999
WWS_16BITDDDD0 ~ 9999

NOTE: T_FBe and C_FBe are exclusive to the FBe model. All other models should use T and C.

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232 (FBs Port0: RS-232 4P Mini-DIN)

HMIDirectionPLC
Pin assignmentsFBs RS232
4P Mini-Din Male
Rx↔ (bidirectional)3 TXD
Tx↔ (bidirectional)4 RXD
GND↔ (bidirectional)2 GND

Diagram 2: RS-232 (FBs Communication Module: RS-232 9P D-Sub)

HMIDirectionPLC
Pin assignmentsFBs Communication Module
RS232 9P D-Sub Male
Rx↔ (bidirectional)2 TX
Tx↔ (bidirectional)3 RX
GND↔ (bidirectional)5 GND

Diagram 3: RS-485 2W (FBs Communication Module 3P Terminal Block)

HMIDirectionPLC
Pin assignmentsFBs Communication Module
3P Terminal
Data-↔ (bidirectional)Data-
Data+↔ (bidirectional)Data+
GND↔ (bidirectional)

Diagram 4: RS-232 (CPU Port: RS-232 15P D-Sub)

HMIDirectionPLC
Pin assignmentsFB CPU Port
RS232
15P D-Sub
Rx↔ (bidirectional)2 TX
Tx↔ (bidirectional)1 RX
GND↔ (bidirectional)6 GND
↕︎ (tie)3 RTS
4 CTS

Diagram 5: RS-485 2W (CPU Port: RS-485 2W 15P D-Sub)

HMIDirectionPLC
Pin assignmentsFB CPU Port
RS485 2W
15P D-Sub Male
Data-↔ (bidirectional)7 Data-
Data+↔ (bidirectional)5 Data+
GND↔ (bidirectional)

Diagram 6: Ethernet