Introduction

All Maple Systems HMI Touch Screens programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Elsist Modbus ASCII. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: SlimLine & Netsyst controllers RS232/485

Website: www.elsist.biz

HMI Setting

ParametersRecommendedOptionsNotes
PLC typeELSIST MODBUS ASCII
PLC I/FRS485RS232/RS485
Baud rate1152009600~115200
Data bits87,8
ParityEvenEven, Odd, None
Stop bits11,2
PLC sta. no.10-254 (255 Broadcast)
Online simulatorYES
BroadcastYES
Extend address modeYES

PLC Setting

Communication mode: Modbus ASCII protocol

Device Address

Bit/WordDevice typeFormatRangeMemo
B%MXDDDDD1 ~ 655350x01 read coil
0x05 write single coil
B%MW_BitDDDDDdd100 ~ 65535150x03 read holding register
0x10 write single register
W%MWDDDDD1 ~ 655350x03 read holding register
0x10 write multiple register
DW%MDDDDDD1 ~ 655350x03 read holding register
0x10 write multiple register

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232

HMIDirectionPLC
Pin assignmentsCOMx RS232
8P RJ45
Rx↔ (bidirectional)6 TX
Tx↔ (bidirectional)5 RX
GND↔ (bidirectional)4 GND

Diagram 2: RS-485 2W

HMIDirectionPLC
Pin assignmentsRS485 2W
3-Way TB
Data-↔ (bidirectional)2 Data-
Data+↔ (bidirectional)1 Data+
GND↔ (bidirectional)3 GND