Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Dersion FFU Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: DERSION FFU Series

HMI Setting

Parameters Recommended Options Notes
PLC type DERSION FFU Series
PLC I/F RS485 2W
Baud rate 9600
Data bits 8
Parity None
Stop bits 1
Retry 1 The number of resending commands

Device Address

Bit/Word Device type Format Range Memo
B DATA DDdd 100 ~ 3015 *Note
W RotatingSpeed DDD 1 ~ 256
W FFU ID DDD 1 ~ 256 Write only
W FFU EmergencyRotatingSpeed DDD 1 ~ 256 Read only
W FFU HighestRotatingSpeed DDD 1 ~ 256 Read only
W FFU LowestRotatingSpeed DDD 1 ~ 256 Read only

*Note: DD = FFU ID; dd values:

  • dd (06): Emergency — Set to on to enter the emergency state, set on again to release.
  • dd (12): Stall
  • dd (13): Over Heat
  • dd (14): Block
  • dd (15): Run Bit

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-485 2W

HMI Direction PLC
Pin assignments RS485 2W
Terminal
Data- ↔ (bidirectional) Data-
Data+ ↔ (bidirectional) Data+
GND ↔ (bidirectional) GND