Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Copley Controls Digital Drives. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Digital Servo Driver & Controllers, Xenus, Xenus Micro, Accelnet, Accelnet Micro, Stepnet series.

Website: http://www.copleycontrols.com/

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeCopley Digital Drives
PLC I/FRS232
Baud rate96009600~115200
Data bits88
ParityNoneEven, Odd, None
Stop bits11
HMI sta. no.0
PLC sta. no.00-127

Device Address

Bit/WordDevice TypeFormatRangeMemo
WFlash INT 16HHH0 ~ 999For Register is INT16 or U16
WRAM INT 16HHH0 ~ 999For Register is INT16 or U16
WFlash INT 32HHH0 ~ 999For Register is INT32 or U32
WRAM INT 32HHH0 ~ 999For Register is INT32 or U32
WRegisterDDDD0 ~ 2457
WT_commandH0
WResetH0
WFlash_INT16_BHHH0 ~ 999
WRAM_INT16_BHHH0 ~ 999
WFlash_INT32_BHHH0 ~ 999
WRAM_INT32_BHHH0 ~ 999
WRegister_BDDDD0 ~ 2457
WT_command_BH0
WReset_BH0
WFlash_INT16_CHHH0 ~ 999
WRAM_INT16_CHHH0 ~ 999
WFlash_INT32_CHHH0 ~ 999
WRAM_INT32_CHHH0 ~ 999
WRegister_CDDDD0 ~ 2457
WT_command_CH0
WReset_CH0
WFlash_INT16_DHHH0 ~ 999
WRAM_INT16_DHHH0 ~ 999
WFlash_INT32_DHHH0 ~ 999
WRAM_INT32_DHHH0 ~ 999
WRegister_DDDDD0 ~ 2457
WT_command_DH0
WReset_DH0

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232 (Xenus, Xenus Micro, Accelnet, Stepnet: 6P RJ11)

HMIDirectionPLC
Pin assignmentsRS232
6P RJ11
Rx↔ (bidirectional)5 TX
Tx↔ (bidirectional)2 RX
GND↔ (bidirectional)3,4 GND

Diagram 2: RS-232 (Accelnet Micro: J5 Cable Connector)

Terminal block connector layout for Copley digital drive showing J1, J3, J4, J5 connectors with numbered pin positions.
HMIDirectionPLC
Pin assignmentsRS232
J5 Cable Connector
Rx↔ (bidirectional)29 TX
Tx↔ (bidirectional)14 RX
GND↔ (bidirectional)15 GND