All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Azbil Controller (CPL). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: SDC/NX/DCP/MQV/MPC/F4H/CMS/MVF/BC-R/AUR/RX
HMI Setting
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | Azbil Controller(CPL) | ||
| PLC I/F | RS485 2W | ||
| Baud rate | 19200 | ||
| Data bits | 8 | ||
| Parity | Even | ||
| Stop bits | 1 | ||
| Series | SDC | SDC/NX/DCP/MQV/MPC/F4H/CMS/MVF/BC-R/AUR/RX | |
| Format | Dec | Dec/Hex | |
| Device Address | 1 | 1~127 | |
| Sub Address | 0 | 0~31 |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | Data_Dec_Bit | DDDDo | 0 ~ 65535F | |
| B | Data_Hex_Bit | DDDDD | 0 ~ FFFFF | |
| W | Data_Dec | DDDDD | 0 ~ 65535 | |
| W | Data_Dec_Sign | DDDDD | 0 ~ 65535 | |
| W | Data_Hex | DDDDD | 0 ~ FFFF |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
RS-485 2W
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS485 2W Terminal |
|
| Data- | ↔ (bidirectional) | Data- |
| Data+ | ↔ (bidirectional) | Data+ |
| GND | ↔ (bidirectional) | GND |