Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Rockwell/Allen-Bradley Micro850 (Ethernet) Free Tag Names PLC. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Rockwell Micro820/850 Ethernet Module

Website: rockwellautomation.com

HMI Setting

ParametersRecommendedOptionsNotes
PLC typeRockwell/Allen-Bradley Micro850 (Ethernet) – Free
PLC I/FEthernet
Port no.44818
HMI sta. no.0
PLC sta. no.1
Protocol (Multiple Service Packet)Disable (Default)Disable/Enable*Note

NOTE: Model: 2080-L50E, 2080-L70E supports Multiple Service Packet Protocol, the firmware version needs to be upgraded to v22 or above.

Support Device Type

Data TypeEBPro (EasyBuilder) Data FormatMemo
Boolbit
Byte16-bit BCD, Hex, Binary, Unsigned8-bit
SInt16-bit BCD, Hex, Binary, Signed8-bit
USInt16-bit BCD, Hex, Binary, Unsigned8-bit
Word16-bit BCD, Hex, Binary, Unsigned16-bit
Int16-bit BCD, Hex, Binary, Signed16-bit
UInt16-bit BCD, Hex, Binary, Unsigned16-bit
DWord32-bit BCD, Hex, Binary, Unsigned32-bit
DInt32-bit BCD, Hex, Binary, Signed32-bit
Real32-bit Float32-bit
UDInt32-bit BCD, Hex, Binary, Unsigned32-bit
StringASCII ObjectLength=word
LINT64-bit Signed64-bit

NOTE: EBPro V6.03.02 or later supports 64-bit data type (cMT Series only), but please note that the address limit range is 48 bits in maximum.

Export and Import Tags

The Connected Components Workbench software terms for Controller Tags are Global Variables and Local Tags are called Local Variables.

  1. Export Controller Tags

    Right-click the Micro800 controller icon in the Project Organizer and select Export u0026gt; Variables. Browse to the desired directory, enter a filename, and click Save. The file is saved in the Microsoft Excel format.
    Connected Components Workbench right-click context menu on Micro800 controller showing Export > Variables option highlighted.
  2. Open EBPro (EasyBuilder) System Parameters

    Open the EBPro (EasyBuilderPro) software, enter System Parameters and add a Rockwell Micro850 device. Navigate to System Parameter Settings u0026gt; Device u0026gt; Select Driver u0026gt; Import Tags.
    EasyBuilderPro System Parameter Settings device list showing Rockwell Micro850 Free Tag Names device with Import Tags button highlighted.
  3. Select Import File Type

    Choose the appropriate import file type:nn- Import Files (.XLS, .XLSX): Rockwell Soft Export Tag Filen- Import Files (*.CSV): EBPro (EasyBuilderPro) Export Tag File
    EasyBuilder Pro Import Tags dialog with Import Files (*.L5X) — Hierarchical type selected and OK button visible.
  4. Select Tags and Confirm

    Select the imported tags, then press OK.
    EasyBuilderPro Tag Manager dialog showing Device_tags tree with PE_ONE through PE_FOUR folders and GoodProduct array tags selected.
  5. Enable Binary Access

    For SINT, INT, or DINT type tags, choose whether to enable binary access.
    EasyBuilderPro dialog asking whether to enable binary access for SINT, INT, or DINT type tags with Yes and No buttons.
  6. Confirm Successful Import

    Import tag information successfully.
    This driver allows you to select multiple spreadsheets (XLS or XLSX) at once when importing tags in EasyBuilderPro, so you can import Global Variables and I/O tags simultaneously.
    EasyBuilderPro confirmation dialog stating imported tag information successfully with OK button.

Wiring Diagram

The diagram below shows the Ethernet cable wiring.

Ethernet straight-through cable wiring diagram showing all 8 color-coded pairs connected pin-to-pin between both ends.