Analog TC Module

IO-SA0400T
$315.00

Analog TC Module converts thermocouples (K, J, E, T, B, R, S, N) into 14-bit digital value.

Compare with other PLCs we offer

Share the product:

Functional

Type
Thermocouple
Temperature Input Range
K: -200.0 – 1200.0°C; J: -200.0 – 800.0°C; E: -200.0 – 600.0°C; T: -200.0 – 400.0°C; B: 400.0 – 1800.0°C; R: 0.0 – 1750.0°C; S: 0.0 – 1750.0°C; N: -200.0 – 1250.0°C
Wire Disconnection Detection
Each channel
Number of Input Channels
4
Max Conversion Rate
50 ms/4 Channels
Insulation Type
Photocoupler between input terminal and PLC power
Accuracy
±[(Full Scale) x 0.3% + 1°C (RJC Error)]

Electrical

Current Consumption +3.3V
40 mA
Current Consumption +24V
10 mA

Mechanical

Dimensions WxHxD
90 x 20 x 60 mm (3.5 x 0.8 x 2.4 in)
Weight
87 g (0.19 lb)
Shock
15G
Vibration
0.5G – Continuous, 1G – Discontinuous
Square Wave Impulse Noise
±2 kV
ESD Immunity
±4 kV – Contact Discharges, ±8 kV – Air Discharges
Radiated Electromagnetic Immunity
80–1000 MHz, 10 V/m
Surge Transient Immunity
2 kV – CPU, Power; 2 kV – Digital I/O (VAC); 1 kV – Digital I/O (VDC); 1 kV – Communication

Environmental

Operating Temperature
-10 – 65 °C (14 – 149 °F)
Storage Temperature
-25 – 80 °C (-13 – 176 °F)
Operating/Storage Relative Humidity
5 – 95% Non-condensing

Certification

CE
Yes
UL
Yes
Maple Systems HMI and PLC

Connect a Maple Systems HMI to a Maple Systems PLC

PLC with Expansion Module

Unbox a PLC, add expansion modules, download a project, and show automatic I/O module detection

Customers who bought this product also bought:

When you order the IO-SA0400T the following items are included in the box:

  • IO-SA0400T
  • Product Manual

Have you used this product? Share your thoughts and help others make the best choice!

Leave a Review