The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with PATLITE VM/VMS Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: PATLITE VM/VMS Series

Website: http://www.patlite.co.jp

HMI Setting

ParametersRecommendedOptionsNotes
PLC typePATLITE VM/VMS Series
PLC I/FRS232RS232 / RS485 2W / RS485 4W / Ethernet
Baud rate384009600 ~ 115200
Data bits87, 8
ParityEvenEven, Odd, None
Stop bits11, 2
PLC sta. no.00 ~ 31
Port no.10600

Device Address

Bit/WordDevice typeFormatRangeMemo
BLAW_bitHHHHh1 ~ 7FFEh: Bit no. (0 ~ f)
WLAWHHHH1 ~ 7FFE
WLAW6ModeH6
WLAW6StyleH6
WLAW6ScaleH6
WLAW6BG_cH6
WLAW6Chr_cH6
WUNI2sJISHHHH1 ~ 7FFELAW: Unicode to Shift-JIS
WUNI2BIG5HHHH1 ~ 7FFELAW: Unicode to BIG5

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232

HMIDirectionPLC
Pin assignmentsRS232 9P D-Sub Female
Rx↔ (bidirectional)3 TXD
Tx↔ (bidirectional)2 RXD
GND↔ (bidirectional)5 GND

Diagram 2: RS-485 2W

HMIDirectionPLC
Pin assignmentsRS485 2W Terminal
Data-↔ (bidirectional)11 Data-
Data+↔ (bidirectional)10 Data+
GND↔ (bidirectional)

Diagram 3: RS-485 4W

HMIDirectionPLC
Pin assignmentsRS485 4W Terminal
Rx-↔ (bidirectional)12 TX-
Rx+↔ (bidirectional)13 TX+
Tx-↔ (bidirectional)11 RX-
Tx+↔ (bidirectional)10 RX+
GND↔ (bidirectional)

Diagram 4: Ethernet

Straight-through Ethernet cable wiring showing all 8 color-coded twisted pairs connected pin-for-pin between both ends.