Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with ODVA General EtherNet/IP (Implicit Messaging). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: ODVA General EtherNet/IP Implicit Messaging Device

HMI Setting

ParametersRecommendedOptionsNotes
PLC typeODVA General EtherNet/IP
PLC I/FEthernet
Port no.44818
Assembly instanceInput: 101
Output: 111
Config: 0
Max: 512 Byte (Input)
Max: 512 Byte (Output)
MulticastDisableDisable / Enable
Electronic keyNoneUse / None
Online simulatorYES
Multiple device connectionsNO

Standard Production Data

Standard Production Data table showing assembly instances (Input 120, Output 112, Configuration 128), data produced byte map, and data consumed fields for EtherNet/IP Implicit Messaging.

Parameter Settings

Parameter Settings dialog with Requested Packet Interval set to 50ms, Assembly instance sizes Input 120 and Output 112 in 8-bit, Multicast set to Disable, and Electronic key set to None.

Device Address

Bit/WordDevice typeFormatRangeMemo
BInput_BitDDDdd0 ~ 51215
BOutput_BitDDDdd0 ~ 51215
WInputDDD0 ~ 512
WOutputDDD0 ~ 512

Wiring Diagram

The diagram below shows the Ethernet cable wiring.

Ethernet straight-through cable wiring diagram showing all 8 color-coded wire pairs connected pin-to-pin from one end to the other.