The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Mitsubishi iQ-R Series (Binary Mode, Symbolic Addressing, Ethernet). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Mitsubishi R00/R01/R02/R04/R08/R16/R32/R120/R04EN /R08EN/R16EN/ R32EN/ R120EN/ R08P/R16P/R32P/R120P/R08SF/R16SF/ R32SF/ R120SF/R08PSF/R16PSF/R32PSF/R120PSF CPU Ethernet Module, M80 CNC Controller

Website: http://www.mitsubishi-automation.com

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeMitsubishi iQ-R Series – Binary Mode (Symbolic Addressing) (Ethernet)
PLC I/FEthernet
Port no.4999
Station No.255
Network number00 ~ 999

PLC Settings

ParameterValue
Communication Data CodeBinary
GX Works3 R08CPU Module Parameter screen with Communication Data Code set to Binary and External Device Configuration highlighted.

External Device Configuration

External Device Configuration: Add SLMP Connection Modules and set different port numbers to use when multiple HMIs communicate at the same time.

Ethernet Configuration window showing four SLMP Connection Modules assigned port numbers 4999, 4998, 4997, and 1025 for simultaneous HMI connections.

Remote Password Setting

Set a remote password and a target connection in the engineering tool, and write the data to the CPU module.

EBPro (EasyBuilder Pro) Device Settings

Navigation: Navigation WindowSystem ParameterDeviceDriver SettingsRemote Password Setting

EBPro (EasyBuilder Pro) Device Settings dialog showing Remote Password Setting enabled with a password entered and Network number set to 0.

GX Works3 Setting Screen

GX Works3 Remote Password Setting dialog listing CPU Module (Built-in Ethernet Function) as the target connection with Detail Setting option.

Import Tags

  1. Create Global Labels and Structured Data Types

    Create data in Global Label and Structured Data Types in GX Works3.
  2. Enable Access from External Device

    In Global Label, the Access from External Device setting must be checked for each label to enable communication with the PLC.
  3. Export Global Label and Structured Data Type Files

    Export Global Label and Structured Data Types as separate label files. Right-click each item in the navigation tree and select Export to File…
    GX Works3 navigation tree with right-click context menu open on Global Label M+Global, showing Export to File option highlighted.
    GX Works3 navigation tree with right-click context menu open on a Structured Data Type entry, showing Export to File option highlighted.
  4. Open Tag Manager in EBPro (EasyBuilder Pro)

    After adding a driver in EBPro (EasyBuilder Pro), open System Parameter Settings and click Tag Manager.
    EasyBuilder Pro System Parameter Settings Device tab showing the configured Mitsubishi iQ-R Series driver with the Tag Manager button highlighted.
  5. Import Global Label File

    In the Mitsubishi Tag Manager, select the Label tab and click Import… to import the Global Label file (single file).
    Mitsubishi Tag Manager Label tab listing imported tags such as S32S32, TimerTimer, and Float64_Array with their data types, and the Import button at the bottom.
  6. Import Structure Data Type Tags

    Select the Data Type tab and click Import… to import Structure Data Type tag files. Multiple files can be imported at the same time.
    Mitsubishi Tag Manager Data Type tab showing imported structured data types including COUNTER, LCOUNTER, LRETENTIVETIMER, LTIMER, RETENTIVETIMER, and TIMER.

Support Device Type

Data typeEasyBuilder data formatMemo
Bitbit
Word [Unsigned]16-bit BCD, Hex, Binary, Unsigned16-bit
Word [Signed]16-bit BCD, Hex, Binary, Signed16-bit
Double Word [Unsigned]32-bit BCD, Hex, Binary, Unsigned32-bit
Double Word [Signed]32-bit BCD, Hex, Binary, Signed32-bit
Float [Single Precision]32-bit Float32-bit
Float [Double Precision]64-bit Double64-bit
String (32)*Note1
Timer
Counter
Long Counter
Retentive Timer
Long Retentive Timer
Long Timer

NOTE: *Note1: String (32) arrays are not supported.

NOTE: *Note2: Tag name length cannot exceed 30 characters.

NOTE: *Note3: String [Unicode] (32), Time and Pointer are not supported.

Wiring Diagram

The diagram below shows the Ethernet cable wiring.

Ethernet cable wiring diagram showing the color-coded twisted pair connections for both ends: W/Orange, Orange, W/Green, Blue, W/Blue, Green, W/Brown, and Brown.