The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Mitsubishi FX3U (Ethernet). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Mitsubishi FX SERIES, Module: FX3U-ENET, FX3U-ENET-ADP

Website: http://www.mitsubishi-automation.com

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeMitsubishi FX3U (Ethernet)
PLC I/FEthernet
Port no.5001 (default)Refer to Module Setting
PLC sta. no.0 (default)Refer to Module Setting

PLC Settings

FX3U-ENET Module Setting

Before using the Ethernet module, use GX Developer / FX Configurator-EN to configure the Ethernet module. The FX3U-ENET module setting steps are shown below.

  1. Open GX Developer Online menu

    Open GX Developer and select Read from PLC in the Online menu.
    GX Developer Online menu open with Read from PLC highlighted.
  2. Select FXCPU PLC series

    In the Select PLC series dialog, choose FXCPU and click OK.
    Select PLC series dialog with FXCPU selected in the dropdown.
  3. Connect PLC via serial port

    Connect the PLC via serial port to set the IP address. In the Transfer Setup window, select RS-232C as the PC side I/F serial setting, set COM port to COM 1, and set Transmission speed to 115.2Kbps.
    Transfer Setup window showing PC side I/F Serial setting dialog with RS-232C selected and COM 1 at 115.2Kbps.
  4. Open FX Configurator-EN

    After finishing the PLC settings, select Tools u0026gt; FX special function utility u0026gt; FX Configurator-EN.
    GX Developer Tools menu with FX special function utility submenu open and FX Configurator-EN highlighted.
  5. Select Module 0 in Ethernet settings

    In FX Configurator-EN, select Module 0 in the Ethernet Module settings list.
    If more than one module is needed, set each module step by step.
    FX Configurator-EN Ethernet settings window with Module 0 selected in the Ethernet Module settings list.
  6. Configure Ethernet operational settings

    In Ethernet operational settings, select the related parameters and IP address, then press End to finish setting.
    FX Configurator-EN Ethernet operational settings showing IP address 192.168.1.180, Binary code, and Ethernet V2.0 frame settings.
  7. Configure Ethernet open settings

    In Ethernet open settings, set the parameters below and press End.
    The first Protocol row uses GX Developer to communicate with the module. The maximum number of Fixed buffer communication procedure units is 4.
    Ethernet open settings table rows 1-4 showing TCP protocol with MELSOFT connection and Unpassive open system at port 5001.
    FX Configurator-EN Ethernet open settings dialog with rows 1-4 configured for TCP, showing MELSOFT connection and Unpassive with port 5001.

Or, for the FX3U-ENET-L module, use the FX3U-ENET-L Configuration Tool with the equivalent Ethernet open settings:

FX3U-ENET-L Configuration Tool Ethernet open settings showing rows 3 and 4 with TCP Unpassive(MC) and MELSOFT connection at port 5001.

Restart and Verify Ethernet Module

  1. Restart PLC for Ethernet communication

    After setting all PLC parameters, restart the PLC to enable Ethernet communication. Verify the settings by clicking Read in FX Configurator-EN to read back from the Ethernet module.
    FX Configurator-EN Ethernet settings with Read form Ethernet Moduls dialog open, showing COM1-115.2Kbps connection interface.

Import Tags

Export from GX Works2

In MELSOFT Series GX Works2, navigate to Global Label Setting and select Write to CSV File to export the tag database.

GX Works2 Global Label Setting with right-click context menu showing Write to CSV File option.

Import into EBPro (EasyBuilder Pro)

In EBPro (EasyBuilder Pro), navigate to System Parameter Settings > Device > Driver > Import Tags to import the exported CSV file.

EBPro (EasyBuilder Pro) Add Tags dialog showing imported address tags data (D-0) and time_0 (TV-0) from GX Works2 CSV.

Device Address

Bit/WordDevice typeFormatRangeMemo
BXOOO0 ~ 571Input
BYOOO0 ~ 571Output Relay
BMDDDD0 ~ 7999Internal Relay
BTDDD0 ~ 511Timer Contacts
BCDDD0 ~ 255Counter Contacts
BSMDDDD8000 ~ 8511Special Int. Relays
BD_BitDDDDDdd0 ~ 1799915Data Register Bit Access
BSDDDD0 ~ 4095Step Relays
WTVDDD0 ~ 511Timer Value
WCVDDD0 ~ 199Counter Value
WDDDDD0 ~ 7999Data Registers
WCV2DDD200 ~ 255Counter Value
WSDDDDD8000 ~ 8511Special Data Registers
WRDDDDD0 ~ 32767File Register

Wiring Diagram

NOTE: Use a standard straight-through Ethernet cable to connect the HMI to the FX3U-ENET module.

The diagram below shows the Ethernet cable wiring.

Ethernet straight-through cable wiring diagram showing pin-to-pin connections for all 8 color-coded pairs.