The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Micro Trend UTREND UTC Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: MICRO TREND UTREND UTC SERIES

Website: http://www.utrend.com.tw/f-all.htm

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeMICRO TREND UTREND UTC SERIES
PLC I/FRS232
Baud rate384004800 ~ 115200
Data bits87, 8
ParityNoneNone, Even, Odd
Stop bits1

Device Address

Bit/WordDevice typeFormatRangeMemo
BM_BITDDDDh10 ~ 2047f*Note1
DWIDDDD0 ~ 2047Float
DWPDDDDDD0 ~ 432143Float
DWQDDDD0 ~ 2047Float
DWMDDDD1 ~ 2047Float
DWRDDDD0 ~ 1023Float
DWI_INTDDDD0 ~ 2047
DWP_INTDDDDDD0 ~ 432143
DWQ_INTDDDD0 ~ 2047
DWM_INTDDDD1 ~ 2047
DWR_INTDDDD0 ~ 1023
DWI_ASCIIDDDD0 ~ 2047
DWP_ASCIIDDDDDD0 ~ 432143
DWQ_ASCIIDDDD0 ~ 2047
DWM_ASCIIDDDD1 ~ 2047
DWR_ASCIIDDDD0 ~ 1023

NOTE: *Note1: Use M_Bit to match the original software; you need to add 0 (INDEX 0) after the address.

E.g.:

M16 — for EBPro (EasyBuilder Pro) objects should be keyed as M160.

M2 — for EBPro (EasyBuilder Pro) objects should be keyed as M20.

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232

HMIDirectionPLC
Pin assignmentsRS232
9P D-Sub
Male
Rx↔ (bidirectional)3 TX
Tx↔ (bidirectional)2 RX
GND↔ (bidirectional)5 GND