Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with KONNEX KNXnet/IP. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported series: WAGO 750-849
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | KONNEX KNXnet/IP | ||
| PLC I/F | Ethernet | USE UDP | |
| Multi. Cast IP | 224.0.23.12 | ||
| Port no. | 3671 | ||
| Type | KNXnet/IP Tunneling | KNXnet/IP Tunneling KNXnet/IP Routing | *Note |
NOTE: Gateway must be configured when using routing protocol.
Support Device Types
| Data type | EBPro (EasyBuilder) data format | Memo |
|---|---|---|
| Bool | bit | |
| Byte | 16-bit BCD, Hex, Binary, Unsigned | 8-bit |
| SInt | 16-bit BCD, Hex, Binary, Signed | 8-bit |
| USInt | 16-bit BCD, Hex, Binary, Unsigned | 8-bit |
| Word | 16-bit BCD, Hex, Binary, Unsigned | 16-bit |
| Int | 16-bit BCD, Hex, Binary, Signed | 16-bit |
| UInt | 16-bit BCD, Hex, Binary, Unsigned | 16-bit |
| DWord | 32-bit BCD, Hex, Binary, Unsigned | 32-bit |
| DInt | 32-bit BCD, Hex, Binary, Signed | 32-bit |
| Real | 32-bit Float | 32-bit |
| UDInt | 32-bit BCD, Hex, Binary, Unsigned | 32-bit |
| Array | String |
PLC Settings
-
Export Tag File from ETS3
Export the tag file using ETS3 software. In ETS3, open the File menu and select Extract Data (e.g. OPC)… to generate the export file.
-
Add Device in EBPro (EasyBuilder)
In EBPro (EasyBuilder), open System Parameter Settings, add KONNEX KNXnet/IP as a device, and then click Import Tag….
-
Click Import in Tag Manager
In the Tag Manager dialog box, click Import….
-
Select ESF File to Import
Select the.esffile and then click OK to finish importing tags.
Wiring Diagram
The diagram below shows the Ethernet cable wiring.

