The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Emotiontek MCU Controller. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Emotiontek MCU-XP/XP2 Controller

Website: http://www.emotiontek.com

HMI Setting

Parameters Recommended Options Notes
PLC type Emotiontek MCU Controller
PLC I/F RS232 RS232/RS485 2W
Baud rate 38400 9600 ~ 115200
Data bits 8 7,8
Parity None None,Odd,Even
Stop bits 1 1,2
PLC sta. no. 0 0-255

PLC Setting

Parameters Value
Protocol type 1,4

Device Address

Bit/Word Device type Format Range Memo
BX_BitHh0 ~ 5f
BY_BitHh0 ~ 4f
BF_BitDh0 ~ 9f
BM_BitDDDh0 ~ 199f
BT_BitDh0 ~ 0f
BC_BitDh0 ~ 0f
WXD0 ~ 5
WYD0 ~ 4
WFD0 ~ 9
WMDDD0 ~ 199
WTD0
WCD0
WTPDD0 ~ 15
WTCDD0 ~ 15
WCPDD0 ~ 15
WCCDD0 ~ 15
DWPD_XDD0 ~ 99
DWPD_YDD0 ~ 99
DWFDD0 ~ 9
DWDDD0 ~ 9
DWLDDDDD0 ~ 1999

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232

HMI Direction PLC
Pin assignments RS232
9P D-Sub Male
Rx ↔ (bidirectional) 3 TX
Tx ↔ (bidirectional) 2 RX
GND ↔ (bidirectional) 5 GND

Diagram 2: RS-485 2W

HMI Direction PLC
Pin assignments RS485 2W
9P D-Sub Male
Data- ↔ (bidirectional) 8 Data-
Data+ ↔ (bidirectional) 7 Data+
GND ↔ (bidirectional) 5 GND