The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Control Techniques SI-Ethernet Modbus TCP/IP. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Unidrive M400 and SI Ethernet Module

Website: http://www.nidec.com/en-Global/

HMI Setting

ParametersRecommendedOptionsNotes
PLC typeControl Techniques SI-Ethernet Modbus TCP/IP
PLC I/FEthernet
Port no.502
Address modeStandardStandard / Modified

Device Address

Bit/WordDevice typeFormatRangeMemo
BBITSSS.MM.PPP0 ~ 255.99.999Slot.Menu.Parameter
ByteBYTESSS.MM.PPP0 ~ 255.99.999Slot.Menu.Parameter
WWORDSSS.MM.PPP0 ~ 255.99.999Slot.Menu.Parameter
DWDWORDSSS.MM.PPP0 ~ 255.99.999Slot.Menu.Parameter

*The standard addressing mode allows parameters up to 99 to be accessed. For any parameter above 99, the modified addressing mode must be used; however, this mode limits the highest accessible menu number to 63.

Modbus Register Addressing Mode

RegisterDescriptionMinimumMaximumMemo
S.15.013Modbus Register Addressing Mode0 (standard)1 (Modified)8 Bit User Save

When using the macro GetData()/SetData() to set the double word address, you need to multiply the number of words by two.

Wiring Diagram

The diagram below shows the Ethernet cable wiring.

Ethernet straight-through cable wiring diagram showing all 8 color-coded wire pairs connected pin-to-pin from one end to the other.