Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Artrich Inverter AR200/216/600 Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Artrich Inverter AR200/216/600 Series

Website: www.artrich.cn

HMI Setting

Parameters Recommended Options Notes
PLC type Artrich Inverter AR200/216/600 Series
PLC I/F RS485 2W
Baud rate 9600
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 1

Device Address

Bit/Word Device type Format Range Memo
B F3002_bit Hh 0 ~ 0f
B F3003_bit Hh 0 ~ 0f
W F0-0 ~ F0-1 D 0 W/R
W F0-2 D 0 ~ 1 W/R *Note1
W F0-3 ~ F0-178 D 0 W/R
W F2-0 ~ F2-16 D 0 Read only
W F3000 ~ F3001 D 0 Write only
W F3002 ~ F3003 D 0 Read only
W FC01 ~ FC12 D 0 Read only

NOTE: *Note1 Value 0 means write to NAND Flash (Data will be saved after power off.) Value 1 means write to RAM (Data will not be saved after power off.)

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-485 2W (8P RJ45)

HMIDirectionPLC
Pin assignmentsRS485 2W
8P RJ45
Data-↔ (bidirectional)8 Data-
Data+↔ (bidirectional)1 Data+
GND↔ (bidirectional)

Diagram 2: RS-485 2W

HMIDirectionPLC
Pin assignmentsRS485 2W
Terminal
Data-↔ (bidirectional)RS485-
Data+↔ (bidirectional)RS485+
GND↔ (bidirectional)GND