All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Modbus TCP/IP 32Bit. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Modbus RTU TCP/IP device

Website: www.modbus.org

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeMODBUS TCP/IP 32Bit
PLC I/FEthernet
Port no.502
PLC sta. no.10~255

Device Address

Bit/WordDevice typeFormatRangeMemo
B0xDDDDD1 ~ 65535Output bit
B0x_multi_coilsDDDDD1 ~ 65535Write multiple coils
B1xDDDDD1 ~ 65535Input bit (read only)
B3x_BitDDDDDdd100 ~ 6553515Input Register bit (read only)
B4x_BitDDDDDdd100 ~ 6553515Output Register bit
B6x_BitDDDDDdd100 ~ 6553515Output Register bit
W3xDDDDD1 ~ 65535Input Register
W4xDDDDD1 ~ 65535Output Register
W4x_32Bit*DDDDD1 ~ 65535
DW5xDDDDD1 ~ 655354x double word swap
W6xDDDDD1 ~ 655354x single word write

Note 1: 4x_32Bit reads/writes 1 word in each packet and displays a 32-bit data by combining two 16-bit registers.

Note 2: EBPro V6.03.02 or later supports 64 bits data type (cMT Series only), but please note that the address limit range is 48 bits in maximum.

Wiring Diagram

The diagram below shows the Ethernet cable wiring.

Ethernet straight-through cable wiring diagram showing all 8 color-coded wire pairs connected pin-to-pin from one end to the other.