The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Yaskawa Electric MP Series SIO (Extension) PLC. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: YASKAWA MP2200, MP2300, MP2300S, MP9xx communication module.

Website: http://www.yaskawa.com/

HMI Setting

ParametersRecommendedOptionsNotes
PLC typeYASKAWA MP Series SIO (Extension)
PLC I/FRS485RS232/RS485 2w/4w
Baud rate192009600~57600
Data bits8
ParityEven
Stop bits1
PLC sta. no.11-31

Device Address

Bit/WordDevice typeFormatRangeMemo
BSBDDDDh0 ~ 8191F
BIBHHHHh0 ~ FFFFF
BOBHHHHh0 ~ FFFFF
BMBDDDDDh0 ~ 65534F
WSWDDDD0 ~ 8191
WIWHHHH0 ~ FFFF
WOWHHHH0 ~ FFFF
WMWDDDDD0 ~ 65534

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232

HMIDirectionPLC
Pin assignmentsRS232 9P
9D-Sub Male
Rx↔ (bidirectional)2 TX
Tx↔ (bidirectional)3 RX
GND↔ (bidirectional)7 GND

Diagram 2: RS-485 2W

HMIDirectionPLC
Pin assignments217IF-01 RS485
14P Connector
Data-↔ (bidirectional)2, 4 D-
Data+↔ (bidirectional)1, 3 D+
GND↔ (bidirectional)14 GND