The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Panasonic MEWTOCOL7. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Panasonic GT series FP7

Website: pewa.panasonic.com

HMI Setting

ParametersRecommendedOptionsNotes
PLC typePanasonic MEWTOCOL7
PLC I/FRS232 / Ethernet
Baud rate96009600 ~ 115200
Data bits87, 8
ParityOddEven, None, Odd
Stop bits11, 2
PLC sta. no.11 ~ 256
Port no.600011 ~ 65535

PLC Setting

ParameterValue
Communication typeTCP/IP
Open typeServer connection (any destination)
Operating mode settingMEWTOCOL7-COM

Built-in ET-LAN Setting

Built-in ET-LAN setting dialog showing Basic communications information with IPv4 address, subnet mask, default gateway, TCP timer values, and Add-on settings.
Built-in SCU setting dialog with COM0 selected, showing Communication mode set to MEWTOCOL7-COM, Station No. 1, Band rate 115200bps, Data length 8 bits, Parity Odd, Stop bit 1 bit.

Built-in SCU Setting

Built-in ET-LAN setting dialog showing User connection information setting 1 with Communication type TCP/IP, Open type Server connection (any destination), Operating mode setting MEWTOCOL-COM, and Home port number 60001.

Import Tag

  1. Export CSV file from FPWIN Pro 7

    In FPWIN Pro 7, go to ProjectExportVariables as CSV fileAll project variables.
    FPWIN Pro 7 Project menu open showing Export submenu with Variables as CSV file option highlighted and All project variables selected.
  2. Import tags in EBPro (EasyBuilder Pro)

    In EBPro (EasyBuilder Pro), go to System ParameterCreate new driverImport Tags.
    EasyBuilder Pro System Parameter Settings showing the Device tab with a Panasonic MEWTOCOL7 device listed and the Import Tags button highlighted.
    Add Tags dialog listing imported address tag names such as VAR_GLOBAL.BoolArray_0 through BoolArray_26 with Bit address mode and R-series addresses.

Device Address

Bit/WordDevice typeFormatRangeMemo
BXDDDh0 ~ 511fExternal input
BYDDDh0 ~ 511fExternal output
BRDDDDh0 ~ 2047fInternal relay
BLDDDDh0 ~ 1023fLink relay
BTDDDD0 ~ 4095Timer
BCDDDD0 ~ 1023Counter
BPDDDh0 ~ 255fPulse relay
BEDDDD0 ~ 4095Error notification relay
BSRDDDh0 ~ 223fSystem relay
BINSSDDh1000 ~ 9962fDirect input *note1
BOTSSDDh1000 ~ 9962fDirect output *note1
BLD_BitDDDDD.h0 ~ 16383.fLD bit specification
BDT_BitDDDDDD.h0 ~ 999423.fDT bit specification
BUM_BitSSHHHHH.h0 ~ 997FFFF.fUM bit specification *note1
B_XLLLDDDh10000 ~ 999511fExternal input *note2
B_YLLLDDDh10000 ~ 999511fExternal output *note2
B_RLLLDDDDh100000 ~ 9992047fInternal relay *note2
B_LLLLDDDDh100000 ~ 9991023fLink relay *note2
B_TLLLDDDD10000 ~ 9994095Timer *note2
B_CLLLDDDD10000 ~ 9991023Counter *note2
B_PLLLDDDh10000 ~ 999255fPulse relay *note2
B_LD_BitLLLDDDDD.h100000.0 ~ 9991633.fLD bit specification *note2
B_DT_BitLLLDDDDDD.h1000000.0 ~ 999999423.fDT bit specification *note2
WWXDDD0 ~ 511External input word
WWYDDD0 ~ 511External output word
WWRDDDD0 ~ 2047Internal relay word
WWLDDDD0 ~ 1023Link relay word
WWSDDD0 ~ 223System relay word
WLDDDDDD0 ~ 16383Link register
WDTDDDDDD0 ~ 999423Data register
WSDDDD0 ~ 255System register
WWISSDD100 ~ 9962Input register *note1
WWOSSDD100 ~ 9962Output register *note1
WUMSSHHHHH100000 ~ 997FFFFUnit memory *note1
DWTSDDDD0 ~ 4095Timer setting value
DWTEDDDD0 ~ 4095Timer elapsed value
DWCSDDDD0 ~ 1023Counter setting value
DWCEDDDD0 ~ 1023Counter elapsed value
DWIH0 ~ EIndex register
W_WXLLLDDD1000 ~ 999511External input word *note2
W_WYLLLDDD1000 ~ 999511External output word *note2
W_WRLLLDDDD10000 ~ 9992047Internal relay word *note2
W_WLLLLDDDD10000 ~ 9991023Link relay word *note2
W_LDLLLDDDDD100000 ~ 99916383Link register *note2
W_DTLLLDDDDDD1000000 ~ 999999423Data register *note2
DW_TSLLLDDDD10000 ~ 9994095Timer setting value *note2
DW_TELLLDDDD10000 ~ 9994095Timer elapsed value *note2
DW_CSLLLDDDD10000 ~ 9991023Counter setting value *note2
DW_CELLLDDDD10000 ~ 9991023Counter elapsed value *note2

*note1 SS = Slot address (1~99)

*note2 LLL = Local address (Program block)

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232

HMIDirectionPLC
Pin assignmentsRS232
Terminal
Rx↔ (bidirectional)SD
Tx↔ (bidirectional)RD
GND↔ (bidirectional)SG

Diagram 2: Ethernet

Ethernet crossover cable diagram showing 8-wire pin-to-pin connections with color-coded twisted pairs: W/Orange, Orange, W/Green, Blue, W/Blue, Green, W/Brown, Brown crossed between both ends.