The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Panasonic Eco-Power Meters. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: KW1M , KW1M-A , KW9M , KW9M-A

Website: https://www.panasonic-electric-works.com/eu/

HMI Settings

ParametersRecommendedOptionsNotes
PLC typePanasonic Eco-Power Meters
PLC I/FRS485 2W
Baud rate96009600 ~ 115200
Data bits8
ParityOdd
Stop bits1
PLC sta. no.1

Supported Device Types

Data typeEBPro (EasyBuilder) data formatMemo
Boolbit
Byte16-bit BCD, Hex, Binary, Unsigned8-bit
SInt16-bit BCD, Hex, Binary, Signed8-bit
USInt16-bit BCD, Hex, Binary, Unsigned8-bit
Word16-bit BCD, Hex, Binary, Unsigned16-bit
Int16-bit BCD, Hex, Binary, Signed16-bit
UInt16-bit BCD, Hex, Binary, Unsigned16-bit
DWord32-bit BCD, Hex, Binary, Unsigned32-bit
DInt32-bit BCD, Hex, Binary, Signed32-bit
Real32-bit Float32-bit
UDInt32-bit BCD, Hex, Binary, Unsigned32-bit

Import Tags

The file for import must be built in Easy Build Pro\Data Type\PanasonicPowerMeter folder. The user can build the file according to the device types in advance, as shown below.
✭Name : User-defined tag name.
✭Data :Type: Define according to the data length and range.
✭Address : The address of the device.
✭Description : The description about the address.

  1. Select the Driver and Open Station Settings

    In EBPro (EasyBuilder Pro), select [Panasonic Eco-Power Meters] as the driver, then click [Station No. and Device Model].
    EasyBuilder Pro New Device dialog with Panasonic Eco-Power Meters selected as PLC type, RS-485 2W interface, and Station No. and Device Model button highlighted.
  2. Configure Station Number and Device Model

    In the Configure Station No. and Device Model dialog:nn- [Station no.]: Set the station number according to the device. Range is 1–99.n- [Name]: The name of the device.n- [Model]: Models with address tag files saved in Data Typeu005cPanasonicPowerMeter appear in the drop-down list.n- [Add]: Add a new model.n- [Delete]: Delete a model. (At least one model must remain in the list.)n- [Import]: Import the .dat file of the model.n- [Export]: Export the .dat file of the model.n- [OK]: Save and close.n- [Cancel]: Close without saving.
    Configure Station No. and Device Model dialog showing two stations with KW9M and KW9M_ADV models, and the model drop-down list open.
  3. Select Tags in Object Settings

    The imported address tags can be selected in the object settings window.
    Object settings window displaying imported Panasonic KW9M address tags including RS485 parameters and DT register addresses, with RS485 Response time highlighted.

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-485 2W

HMIDirectionPLC
Pin assignmentsPLC RS485 2W
Terminal
Data−↔ (bidirectional)B−
Data+↔ (bidirectional)A+
GND↔ (bidirectional)