The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Siemens TI565. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: SIMATIC TI565

Website: http://www.siemens.com/entry/cc/en/

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeSIMATIC TI565
PLC I/FRS232RS232, RS485 4W
Baud rate1920019200
Data bits77
ParityOddOdd
Stop bits11
PLC sta. no.0Does not apply

Device Address

Bit/WordDevice typeFormatRangeMemo
BCRDDDDD1 ~ 65535Internal Relay
BXDDDDD1 ~ 65535Discrete Input Coils
BYDDDDD1 ~ 65535Discrete Output Coils
BV_BitDDDDDdd101 ~ 6553616User Data Register Bits
WVDDDDD1 ~ 65535User Data Registers
DWVDDDDDD1 ~ 65535User Data Registers (32bit)
WSTWDDDDD1 ~ 65535Status Word Registers
WTCPDDDDD1 ~ 65535Timer/Counter Preset Values
WTCCDDDDD1 ~ 65535Timer/Counter Current Values
WWXDDDDD1 ~ 65535Word Discrete Inputs
WWYDDDDD1 ~ 65535Word Discrete Outputs

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232 (25P D-Sub Male)

HMIDirectionPLC
Pin assignmentsRS232
25P D-Sub
Male
Rx↔ (bidirectional)2 TX
Tx↔ (bidirectional)3 RX
GND↔ (bidirectional)7 GND
↕︎ (tie)4
5
↕︎ (tie)6
8
20

Diagram 2: RS-232 (9P D-Sub Male)

HMIDirectionPLC
Pin assignmentsRS232
9P D-Sub
Male
Rx↔ (bidirectional)3 TX
Tx↔ (bidirectional)2 RX
GND↔ (bidirectional)5 GND
↕︎ (tie)7
8
↕︎ (tie)1
4
6

Diagram 3: RS-485 4W (9P Mini-Din Male)

HMIDirectionPLC
Pin assignmentsRS485 4W
9P Mini-Din
Male
Rx-↔ (bidirectional)7 TXD-
RX+↔ (bidirectional)1 TXD+
Tx-↔ (bidirectional)8 RXD-
Tx+↔ (bidirectional)5 RXD+
GND↔ (bidirectional)6 GND