Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Parker Hannifin ACR9000. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: Parker ACR9000
Website: parkermotion.com
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | Parker ACR9000 | ||
| PLC I/F | RS232 | RS485 4W / RS232 / Ethernet | |
| Baud rate | 38400 | 1200 – 38400 | |
| Data bits | 8 | 7, 8 | |
| Parity | None | Even, Odd, None | |
| Stop bits | 1 | 1, 2 | |
| Port no. | 5006 | ||
| PLC sta. no. | 0 | ||
| Online simulator | YES |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | P_Low16bit | DDDDDdd | 0 ~ 9999915 | |
| B | P_High16bit | DDDDDdd | 0 ~ 9999915 | |
| W | P_Int32 | DDDDD | 0 ~ 99999 | |
| W | P_Float | DDDDD | 0 ~ 99999 |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
Diagram 1: RS-232
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | Parker ACR9000 RS232 9P D-Sub Male | |
| Rx | ↔ (bidirectional) | 3 TXD |
| Tx | ↔ (bidirectional) | 2 RXD |
| GND | ↔ (bidirectional) | 5 GND |
Diagram 2: Ethernet