The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with LS Electric XEC/XGI CPU Direct. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: LS XEC/XGI CPU RS232 port

Website: http://www.lgis.com/

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeLS XEC/XGI CPU DIRECT
PLC I/FRS232RS232
Baud rate1152009600~115200
Data bits87, 8
ParityNoneEven, Odd, None
Stop bits11
PLC sta. no.11
  • Supports communications between HMI and PLC in pass-through mode.
  • Set LW-9903 to 2 to enhance the speed of download/upload PLC program in pass-through mode.

Device Address

Bit/WordDevice TypeFormatRange
BAW_BitDDDDDDh0 ~ 262143f
BIW_BitDDD.DD.Dh0 ~ 127.15.3f
BQW_BitDDD.DD.Dh0 ~ 127.15.3f
BMW_BitDDDDDDDh0 ~ 1048575f
BRW_BitDDDDDh0 ~ 32767f
BWW_BitDDDDDDh0 ~ 524287f
BFW_BitDDDDh0 ~ 4095f
BKW_BitDDDDh0 ~ 8399f
BLW_BitDDDDDh0 ~ 11263f
BNW_BitDDDDDh0 ~ 25087f
BUW_BitDD.DD.DDh0 ~ 31.15.31f
BAXDDDDDDD0 ~ 4194303
BIXDDD.DD.DD0 ~ 127.15.63
BQXDDD.DD.DD0 ~ 127.15.63
BMXDDDDDDDD0 ~ 16777199
BRXDDDDDD0 ~ 524287
BWXDDDDDDD0 ~ 8388607
BFXDDDDDD0 ~ 134399
BKXDDDDDD0 ~ 134399
BLXDDDDDDD0 ~ 1880223
BNXDDDDDD0 ~ 401407
BUXDD.DD.DDD0 ~ 31.15.511
WAWDDDDDD0 ~ 262143
WIWDDD.DD.D0 ~ 127.15.3
WQWDDD.DD.D0 ~ 127.15.3
WMWDDDDDDD0 ~ 1048575
WRWDDDDD0 ~ 32767
WWWDDDDDD0 ~ 524287
WFWDDDD0 ~ 4095
WKWDDDD0 ~ 8399
WLWDDDDD0 ~ 11263
WNWDDDDD0 ~ 25087
WUWDD.DD.DD0 ~ 31.15.31
DWMDDDDDDD0 ~ 524287

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232

HMIDirectionPLC
Pin assignmentsXGI CPU RS232
9P D-Sub
Male
Rx↔ (bidirectional)3
Tx↔ (bidirectional)2
GND↔ (bidirectional)5