Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with LS Electric GM3467 (LOADER). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: LS GLOFA series GM3, GM4, GM6, GM7 CPU port
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | LS GLOFA GM3467 (LOADER) | ||
| PLC I/F | RS232 | ||
| Baud rate | 38400 | ||
| Data bits | 8 | ||
| Parity | None | ||
| Stop bits | 1 | ||
| PLC sta. no. | 1 |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | MX | DDDDDD | 0 ~ 524272 | |
| B | IX | ddDdd | 0 ~ 63763 | 00.0.0 ~ 63.7.63 (dd.D.dd) |
| B | QX | ddDdd | 0 ~ 63763 | 00.0.0 ~ 63.7.63 (dd.D.dd) |
| W | IW | HHH | 0 ~ 273 | |
| W | QW | HHH | 0 ~ 273 | |
| W | MW | DDDDD | 0 ~ 32767 | |
| W | MD | DDDDD | 0 ~ 16383 |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
RS-232 (LS GLOFA Series)
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS232 9P D-Sub Male |
|
| Rx | ↔ (bidirectional) | 3 |
| Tx | ↔ (bidirectional) | 2 |
| GND | ↔ (bidirectional) | 5 |