Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Koyo (Automation Direct) Do-more PLC. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: Do-more H2 Series PLC
Website: http://www.automationdirect.com
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | KOYO Do-more | ||
| PLC I/F | RS232 | ||
| Baud rate | 115200 | 9600 ~ 115200 | |
| Data bits | 8 | ||
| Parity | None | ||
| Stop bits | 1 | ||
| PLC sta. no. | 1 | ||
| Online simulation | YES | ||
| Extend address mode | NO |
PLC Settings
| Parameter | Value |
|---|---|
| Serial Port Mode | Do-more programming |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | ST | DDDD | 0 ~ 1023 | |
| B | X | DDDDD | 0 ~ 65535 | |
| B | Y | DDDDD | 0 ~ 65535 | |
| B | C | DDDDD | 0 ~ 65535 | |
| B | MI | DDDDD | 0 ~ 65535 | |
| B | MC | DDDDD | 0 ~ 65535 | |
| B | T.Done | DDDDD | 0 ~ 32766 | Read only |
| B | CT.Done | DDDDD | 0 ~ 32766 | Read only |
| B | DLX | OOOOOO | 0 ~ 177777 | |
| B | DLY | OOOOOO | 0 ~ 177777 | |
| B | DLC | OOOOOO | 0 ~ 177777 | |
| W | DLV | OOOOOO | 0 ~ 177777 | |
| W | SDT | D.D | 0 ~ 7.6 | *Note 1 |
| W | WX | DDDDD | 0 ~ 65535 | |
| W | WY | DDDDD | 0 ~ 65535 | |
| W | V | DDDDD | 0 ~ 65535 | |
| W | N | DDDDD | 0 ~ 65535 | |
| W | SS | DDDD.DD | 0 ~ 3854.34 | Read only *Note 2 |
| W | SL | DDDD.DDD | 0 ~ 1007.130 | Read only *Note 2 |
| W | UDT | DDDDD.D | 0 ~ 32767.6 | *Note 1 |
| W | PL | DDD | 0 ~ 255 | |
| W | MIR | DDDDD | 0 ~ 65535 | |
| W | MHR | DDDDD | 0 ~ 65535 | |
| W | DST | DDD | 0 ~ 511 | |
| W | D | DDDDD | 0 ~ 65534 | |
| W | R | DDDDD | 0 ~ 65534 | Real Number (float) |
| W | T.ACC | DDDDD | 0 ~ 32766 | |
| W | CT.ACC | DDDDD | 0 ~ 32766 |
*Note 1: SDT, UDT: xxx.0 = Year, xxx.1 = Month, xxx.2 = Day, xxx.3 = DayOfWeek, xxx.4 = Hour, xxx.5 = Minute, xxx.6 = Second.
*Note 2: SS, SL: xxx.0 = MaxLen, xxx.1 = Length, xxx.2 ~ 34 = String (SS); xxx.2 ~ 130 = String (SL).
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
RS-232
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | Koyo H2 Series RS232 6P RJ12 | |
| Rx | ↔ (bidirectional) | 4 |
| Tx | ↔ (bidirectional) | 3 |
| GND | ↔ (bidirectional) | 1 |
| RTS | ↔ (bidirectional, optional) | 6 |
| CTS | ↔ (bidirectional, optional) | 5 |