Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Koyo (Automation Direct) Do-more PLC. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Do-more H2 Series PLC

Website: http://www.automationdirect.com

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeKOYO Do-more
PLC I/FRS232
Baud rate1152009600 ~ 115200
Data bits8
ParityNone
Stop bits1
PLC sta. no.1
Online simulationYES
Extend address modeNO

PLC Settings

ParameterValue
Serial Port ModeDo-more programming

Device Address

Bit/WordDevice typeFormatRangeMemo
BSTDDDD0 ~ 1023
BXDDDDD0 ~ 65535
BYDDDDD0 ~ 65535
BCDDDDD0 ~ 65535
BMIDDDDD0 ~ 65535
BMCDDDDD0 ~ 65535
BT.DoneDDDDD0 ~ 32766Read only
BCT.DoneDDDDD0 ~ 32766Read only
BDLXOOOOOO0 ~ 177777
BDLYOOOOOO0 ~ 177777
BDLCOOOOOO0 ~ 177777
WDLVOOOOOO0 ~ 177777
WSDTD.D0 ~ 7.6*Note 1
WWXDDDDD0 ~ 65535
WWYDDDDD0 ~ 65535
WVDDDDD0 ~ 65535
WNDDDDD0 ~ 65535
WSSDDDD.DD0 ~ 3854.34Read only *Note 2
WSLDDDD.DDD0 ~ 1007.130Read only *Note 2
WUDTDDDDD.D0 ~ 32767.6*Note 1
WPLDDD0 ~ 255
WMIRDDDDD0 ~ 65535
WMHRDDDDD0 ~ 65535
WDSTDDD0 ~ 511
WDDDDDD0 ~ 65534
WRDDDDD0 ~ 65534Real Number (float)
WT.ACCDDDDD0 ~ 32766
WCT.ACCDDDDD0 ~ 32766

*Note 1: SDT, UDT: xxx.0 = Year, xxx.1 = Month, xxx.2 = Day, xxx.3 = DayOfWeek, xxx.4 = Hour, xxx.5 = Minute, xxx.6 = Second.

*Note 2: SS, SL: xxx.0 = MaxLen, xxx.1 = Length, xxx.2 ~ 34 = String (SS); xxx.2 ~ 130 = String (SL).

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232

HMIDirectionPLC
Pin assignmentsKoyo H2 Series
RS232 6P
RJ12
Rx↔ (bidirectional)4
Tx↔ (bidirectional)3
GND↔ (bidirectional)1
RTS↔ (bidirectional, optional)6
CTS↔ (bidirectional, optional)5