Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Danfoss ECL Apex20. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

HMI Setting

ParametersRecommendedOptionsNotes
PLC typeDanfoss ECL Apex20
PLC I/FRS232
Baud rate9600
Data bits8
ParityNone
Stop bits1
PLC sta. no.1

Device Address

Bit/WordDevice typeFormatRangeMemo
BFlagDDDD0 ~ 8191
BOutputDDDD0 ~ 1023
BInputDDDD0 ~ 1023
BReg_BitDDDDDdd0 ~ 1638331dd: Bit no. (00 ~ 31)
DWRegisterDDDDD0 ~ 16383
DWCounterDDDD0 ~ 1599
DWTimerDDDD0 ~ 1599
DWReg_FloatDDDDD0 ~ 16383Support 32-bit float format
WDBnDDDDDDD0 ~ 8191383

NOTE: EBPro (EasyBuilder) device address range may differ from PLC extended mode, please refer to EasyBuilder address range as above.

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1:

RS-232 (ECL Apex20 Controller: 9P D-Sub)

HMIDirectionPLC
Pin assignmentsRS232
9P D-Sub
Male
Rx↔ (bidirectional)3 TX
Tx↔ (bidirectional)2 RX
GND↔ (bidirectional)5 GND
↕︎ (tie)7 RTS
8 CTS

Diagram 2:

RS-485 2W (ECL Apex20 Controller: Terminal)

HMIDirectionPLC
Pin assignmentsECL Apex20 Controller
Port#1 / Port#0
Data-↔ (bidirectional)11 /29 Data-
Data+↔ (bidirectional)12 /28 Data+
GND↔ (bidirectional)