Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Danfoss FC Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: FC051, FC100, FC200, FC300, VLT Micro Driver
Website: http://www.danfoss.com/
HMI Setting
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | Danfoss FC Series | ||
| PLC I/F | RS485 2W | ||
| Baud rate | 9600 | ||
| Data bits | 8 | ||
| Parity | Even | ||
| Stop bits | 1 | ||
| PLC sta. no. | 1 |
Device Address
Para_Index 310.1=31001, Para_Index310.0=31000
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| DW | Parameter | DDDD | 0 ~ 9999 | Set Parameter |
| W | Reference | D | 0 ~ 1 | Control Bus Reference |
| DW | Para_Index |
DDDDDD | 0 ~ 999999 | Set Parameter(Index) |
| W | Parameter_text |
DDDD | 0 ~ 9999 | |
| W | Para_Index_test |
DDDDDD | 0 ~ 999999 |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
RS-485 2W
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | FC RS485 2W Terminal | |
| Data- | ↔ (bidirectional) | 69 Data- |
| Data+ | ↔ (bidirectional) | 68 Data+ |
| GND | ↔ (bidirectional) |
*RW100set PCD1 Control Word of station 1*RW101read PCD1 Status Word of station 1*RW102set PCD1 Control Word of station 2*RW103read PCD1 Status Word of station 2*RW104set PCD1 Control Word of station 3*RW105read PCD1 Status Word of station 3*RW106set PCD1 Control Word of station 4*RW107read PCD1 Status Word of station 4